List Of Parameters And Modbus Holding Registers; Monitor Group - Hitachi WJ Series User Manual

Table of Contents

Advertisement

Chapter 18

18.2 List of Parameters and Modbus Holding Registers

 In the default condition, the data part (0.00 (Hz) in the case of stopped state) of [d001] is always
!
displayed after the power is turned on. To change the monitor at power-on, change the setting
of "Initial display selection [b038]".
 If the parameter code cannot be displayed, or if the code and setting data can be displayed but
cannot be changed, the display restrictions or Soft-Lock may be activated. For more information,
see "7.2 Functions Related to Keypad" or "15.4.1 Troubleshooting Other Than Trip and
Warning".
 The d monitor group can only be Read, and the rest of the parameters can be R/W unless
otherwise noted.
 In the table below, Modbus holding register numbers may be discontinuous, but do not access
the holding registers that is not listed.
18.2.1
d Monitor Group
Code
Name
Output frequency
d001
monitor
Output current
d002
monitor
Rotation direction
d003
monitor
PID feedback
d004
value monitor
Input terminal
d005
monitor
Output terminal
d006
monitor
Output frequency
d007
scale conversion
monitor
Detect speed
d008
monitor
Torque reference
d009
monitor
Torque bias
d010
monitor
Output torque
d012
monitor
Output voltage
d013
monitor
Input power
d014
monitor
Accumulated
d015
input power
monitor
Accumulated
d016
RUN time monitor
Accumulated
d017
power-on time
monitor
Cooling fin
d018
temperature
monitor
List of Parameters/Modbus Coil/Register Numbers
Data range
0.00 to 590.00 (Hz)
0.00 to 655.35 (A)
F (Forward) / o (Stop) / r (Reverse)
0.00 to 100.00
(0.00 to 9999.00 depending on
[A075] gain)
(Example) 1, 2: ON
3 to 8: OFF
(Example) 11, 12: ON
Relay: OFF
0.00 to 590.00 (0.00 to 58994.10
depending on [b086] conversion)
-590.00 to +590.00 (Hz)
-200 to 200 (%)
-200 to 200 (%)
-200 to 200 (%)
0.0 to 600.0 (V)
0.0 to 100.0 (kW)
0.0 to 999900.0
×
(Unit: 1 kW
[b079])
0 to 999000 (hr)
0 to 999000 (hr)
-20.0 to 150.0 (°C)
Change
Modbus communication
during
Register No.
running
1001h (High)
1002h (Low)
-
1003h
-
1004h
1005h (High)
-
1006h (Low)
-
1007h
-
1008h
1009h (High)
100Ah (Low)
100Bh (High)
-
100Ch (Low)
-
100Dh
-
100Eh
-
1010h
-
1011h
-
1012h
1013h (High)
-
1014h (Low)
1015h (High)
-
1016h (Low)
1017h (High)
-
1018h (Low)
-
1019h
18-2-1
Data range
Resolution
0 to 59000
0.01
0 to 65535
0.01
0 to 2
-
0 to 1000
0.1
(0 to 99990)
0
2
: (terminal 1) to
Bit
7
2
: (terminal 8)
0
2
: (11)
1
2
: (12)
Bit
6
2
: (Relay)
0 to 5899410
0.01
-59000 to 59000
0.01
-200 to +200
1
-200 to +200
1
-200 to +200
1
0 to 6000
0.1
0 to 1000
0.1
0 to 9999000
1
0 to 999000
1
0 to 999000
1
-200 to 1500
0.1
Page
10-1-1
10-1-2
10-1-2
9-8-1
10-4-1
10-2-1
10-1-1
10-1-3
10-1-4
10-1-6
10-1-7
10-3-1
10-3-2