Hitachi X200 Series Connection Manual

Hitachi X200 Series Connection Manual

Inverter modbusrtu driver
Hide thumbs Also See for X200 Series:

Advertisement

Inverter MODBUS
RTU Driver
1
System Configuration....................................................................................................... 3
2
External Device Selection ................................................................................................ 6
3
Communication Settings .................................................................................................. 7
4
Setup Items .................................................................................................................... 19
5
Cable Diagrams ............................................................................................................. 23
6
Supported Devices......................................................................................................... 41
7
Device Code and Address Code.................................................................................... 45
8
Error Messages.............................................................................................................. 47
1
Hitachi IES Co., Ltd.

Advertisement

loading

Summary of Contents for Hitachi X200 Series

  • Page 1: Table Of Contents

    Hitachi IES Co., Ltd. Inverter MODBUS RTU Driver System Configuration....................... 3 External Device Selection ....................6 Communication Settings ....................7 Setup Items ........................19 Cable Diagrams ......................23 Supported Devices......................41 Device Code and Address Code..................45 Error Messages......................47...
  • Page 2 Inverter MODBUS RTU Driver Introduction This manual describes how to connect the Display and the External Device (target Inverter). In this manual, the connection procedure is described in the sections identified below: System Configuration "1 System Configuration" (page 3) This section lists the types of External Devices and SIO that you can connect.
  • Page 3: System Configuration

    Inverter MODBUS RTU Driver System Configuration The following table lists system configurations for connecting Hitachi IES Co., Ltd. External Devices and the Display. Series Inverter Link I/F SIO Type Setting Example Cable Diagram Serial port connector RS-422/485 "Setting Example 1"...
  • Page 4 Inverter MODBUS RTU Driver IPC COM Port When connecting IPC with an External Device, the COM port used depends on the series and SIO type. Please refer to the IPC manual for details. Usable port Usable Port Series RS-232C RS-422/485(4 wire) RS-422/485(2 wire) COM1 , COM2,...
  • Page 5 Inverter MODBUS RTU Driver DIP switch setting: RS-422/485 (4 wire) DIP switch Setting Description Reserved (always OFF) SIO type: RS-422/485 Output mode of SD (TXD) data: Always output Terminal resistance (220Ω) insertion to SD (TXD): None Terminal resistance (220Ω) insertion to RD (RXD): None Short-circuit of SDA (TXA) and RDA (RXA): Not available Short-circuit of SDB (TXB) and RDB (RXB): Not available RS (RTS) Auto control mode: Disabled...
  • Page 6: External Device Selection

    Use an integer from 1 to 4 to enter the number of Devices/PLCs to connect to the Number of Devices/PLCs Display. Select the manufacturer of the External Device to be connected. Select "Hitachi IES Manufacturer Co., Ltd.". Select a model (series) of the External Device to be connected and connection method.
  • Page 7: Communication Settings

    Inverter MODBUS RTU Driver Communication Settings This section provides examples of communication settings recommended by Pro-face for the Display and the External Device. Setting Example 1 GP Pro-EX Settings Communication Settings To display the setup screen, from the [System Settings] workspace, select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, select the external device and click [Settings] from...
  • Page 8 Inverter MODBUS RTU Driver External Device Settings For External Device communication settings, use the FUNC key, Up key, Down key, and STR key located in the keypad of the External Device. Refer to your External Device manual for details. Set OPE/485 switch to "485" position. Turn ON the External Device.
  • Page 9 Inverter MODBUS RTU Driver Setting Example 2 GP Pro-EX Settings Communication Settings To display the setup screen, from the [System Settings] workspace, select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, select the external device and click [Settings] from [Device-Specific Settings] in the [Device/PLC] window.
  • Page 10 Inverter MODBUS RTU Driver External Device Settings For External Device communication settings, use the FUNC key, Up key, Down key, and STR key located in the keypad of the External Device. Refer to your External Device manual for details. Turn ON the External Device. Press FUNC key for 3 seconds or longer.
  • Page 11 Inverter MODBUS RTU Driver Setting Example 3 GP Pro-EX Settings Communication Settings To display the setup screen, from the [System Settings] workspace, select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, select the external device and click [Settings] from [Device-Specific Settings] in the [Device/PLC] window.
  • Page 12 Inverter MODBUS RTU Driver External Device Settings For External Device communication settings, use the FUNC key, Up key, Down key, and STR key located in the keypad of the External Device. Refer to your External Device manual for details. Turn ON the External Device. Press FUNC key for 3 seconds or longer.
  • Page 13 Inverter MODBUS RTU Driver Setting Example 4 GP Pro-EX Settings Communication Settings To display the setup screen, from the [System Settings] workspace, select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, select the external device and click [Settings] from [Device-Specific Settings] in the [Device/PLC] window.
  • Page 14 Inverter MODBUS RTU Driver External Device Settings For External Device communication settings, use the FUNC key, Up key, Down key, and STR key located in the keypad of the External Device. Refer to your External Device manual for details. Set OPE/485 switch to "485" position. Turn ON the External Device.
  • Page 15 Inverter MODBUS RTU Driver Setting Example 5 GP Pro-EX Settings Communication Settings To display the setup screen, from the [System Settings] workspace, select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, select the external device and click [Settings] from [Device-Specific Settings] in the [Device/PLC] window.
  • Page 16 Inverter MODBUS RTU Driver External Device Settings For External Device communication settings, use the FUNC key, Up key, Down key, and STR key located in the keypad of the External Device. Refer to your External Device manual for details. Set OPE/485 switch to "485" position. Turn ON the External Device.
  • Page 17 Inverter MODBUS RTU Driver Setting Example 6 GP Pro-EX Settings Communication Settings To display the setup screen, from the [System Settings] workspace, select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the External Device and click [Settings].
  • Page 18 Inverter MODBUS RTU Driver External Device Settings To define the External Device communication settings, use the External Device keypad’s STOP/RESET, ESC, Up, Down, and SET keys. Refer to your External Device manual for details. Turn ON the External Device. Press STOP/RESET to stop operations. Press ESC to move to the Function Group.
  • Page 19: Setup Items

    Inverter MODBUS RTU Driver Setup Items Set up the Display’s communication settings in GP Pro-EX or in the Display’s offline mode. The setting of each parameter must match that of the External Device. "3 Communication Settings" (page 7) Setup Items in GP Pro-EX Communication Settings To display the setup screen, from the [System Settings] workspace, select [Device/PLC].
  • Page 20 Inverter MODBUS RTU Driver Setup Items Setup Description Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the Timeout response from the External Device. In case of no response from the External Device, use an integer from 0 to 255 to enter how Retry many times the Display retransmits the command.
  • Page 21 Inverter MODBUS RTU Driver Setup Items in Offline Mode • Refer to the Maintenance/Troubleshooting Guide for information on how to enter offline mode or about the operation. Cf. Maintenance/Troubleshooting Guide "Offline Mode" • The number of the setup items to be displayed for 1 page in the offline mode depends on the Display in use.
  • Page 22 Inverter MODBUS RTU Driver Setup Items Setup Description Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the Timeout (s) response from the External Device. In case of no response from the External Device, use an integer from "0 to 255" to enter how Retry many times the Display retransmits the command.
  • Page 23: Cable Diagrams

    Inverter MODBUS RTU Driver Cable Diagrams The following cable diagrams may be different from cable diagrams recommended by Hitachi IES Co., Ltd. Please be assured there is no operational problem in applying the cable diagrams shown in this manual. •...
  • Page 24 Inverter MODBUS RTU Driver Only the COM port which can communicate by RS-422/485 (2 wire) can be used. " IPC COM Port" (page 4) • 1:1 Connection Display side Terminal Block Shield Signal name Termination TERM resistance External Device side 200Ω...
  • Page 25 Inverter MODBUS RTU Driver • 1:1 Connection Display side D-Sub 9pin (socket) Termination Signal name Shield resistance External Device side 200Ω RJ45 connector Termination Display Signal name resistance 200Ω Shell • 1:n Connection Display side D-Sub 9pin (socket) Termination Signal name Shield resistance External Device side...
  • Page 26 Inverter MODBUS RTU Driver • 1:1 Connection Display side Terminal Block Signal name Shield Termination TERM resistance External Device side 200Ω Display RJ45 connector Termination Signal name resistance 200Ω CA3-ADPTRM-01 CA4-ADPONL-01 User-created cable • 1:n Connection Display side Terminal Block Signal name Shield Termination...
  • Page 27 Inverter MODBUS RTU Driver • 1:1 Connection Display side D-Sub 9pin (plug) Shield Signal name Termination resistance TERMRX External Device side 200Ω RJ45 connector Display Termination Signal name resistance 200Ω TERMTX CA4-ADPONL-01 Shell User-created cable • 1:n Connection Display side D-Sub 9pin (plug) Shield Signal name...
  • Page 28 Inverter MODBUS RTU Driver • 1:1 Connection External Device side Terminal Block External Device side Shield Signal name RJ45 connector Termination Termination TERM Signal name resistance resistance 200Ω 200Ω Display CA3-ADPTRM-01 CA3-ADPCOM-01 User-created cable • 1:n Connection External Device side Terminal Block External Device side External Device side...
  • Page 29 Inverter MODBUS RTU Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) RJ45 connector Termination Termination resistance Signal name Signal name Shield resistance 200Ω 200Ω DATA+ Display DATA- GND(SG) Shell • 1:n Connection Display side External Device side External Device side D-Sub 9pin (socket) RJ45 connector...
  • Page 30 Inverter MODBUS RTU Driver • 1:1 Connection Display side Terminal block Termination Signal name Shield External Device side resistance*1 RJ45 connector Termination Display Signal name resistance 200Ω • 1:n Connection Display side Terminal block Signal name Termination Shield External Device side External Device side resistance*1 RJ45 connector...
  • Page 31 Inverter MODBUS RTU Driver • 1:1 Connection Display side External Device side D-Sub 9pin (plug) RJ45 connector Termination Termination resistance Signal name Signal name Shield resistance 200Ω 200Ω LINE(+) Display LINE(-) GND(SG) RS(RTS) Shell • 1:n Connection Display side External Device side External Device side D-Sub 9pin (plug) RJ45 connector...
  • Page 32 Inverter MODBUS RTU Driver Cable Diagram 2 Display Cable Notes (Connection Port) COM port conversion adapter by Pro-face CA3-ADPCOM-01 GP3000 (COM1) Terminal block conversion adapter by Pro-face AGP-3302B (COM2) CA3-ADPTRM-01 (COM2) LT (COM1) User-created cable User-created cable Online adapter by Pro-face CA4-ADPONL-01 Terminal block conversion adapter by Pro-face CA3-ADPTRM-01...
  • Page 33 Inverter MODBUS RTU Driver • 1:1 Connection Display side Terminal Block Shield Signal name Termination TERM resistance External Device side 200Ω TM2 Terminal Block Display Signal name CA3-ADPTRM-01 CA3-ADPCOM-01 User-created cable • 1:n Connection Display side Terminal Block Shield Signal name Termination TERM resistance...
  • Page 34 Inverter MODBUS RTU Driver • 1:1 Connection Display side D-Sub 9pin (socket) Termination Signal name Shield resistance External Device side 200Ω TM2 Terminal Block Display Signal name Shell • 1:n Connection Display side D-Sub 9pin (socket) Termination Signal name Shield resistance External Device side External Device side...
  • Page 35 Inverter MODBUS RTU Driver • 1:1 Connection Display side Terminal Block Signal name Shield Termination TERM resistance External Device side 200Ω Display TM2 Terminal Block Signal name CA3-ADPTRM-01 CA4-ADPONL-01 User-created cable • 1:n Connection Display side Terminal Block Signal name Shield Termination TERM...
  • Page 36 Inverter MODBUS RTU Driver • 1:1 Connection Display side D-Sub 9pin (plug) Signal name Shield Termination TERMRX resistance External Device side 200Ω Display TM2 Terminal Block Signal name TERMTX CA4-ADPONL-01 Shell User-created cable • 1:n Connection Display side D-Sub 9pin (plug) Signal name Shield Termination...
  • Page 37 Inverter MODBUS RTU Driver • 1:1 Connection Display side Terminal Block External Device side Shield Signal name TM2 Terminal Block Termination Signal name TERM resistance 200Ω Display CA3-ADPTRM-01 CA3-ADPCOM-01 User-created cable • 1:n Connection Display side Terminal Block External Device side External Device side Shield Signal name...
  • Page 38 Inverter MODBUS RTU Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) TM2 Terminal Block Termination Signal name Signal name Shield resistance 200Ω DATA+ Display DATA- GND(SG) Shell • 1:n Connection Display side External Device side External Device side D-Sub 9pin (socket) TM2 Terminal Block TM2 Terminal Block...
  • Page 39 Inverter MODBUS RTU Driver • 1:1 Connection Display side Terminal block Signal name Shield Termination External Device side resistance*1 TM2 Terminal Block Display Signal name • 1:n Connection Display side Terminal block Signal name Shield Termination External Device side External Device side resistance*1 TM2 Terminal Block TM2 Terminal Block...
  • Page 40 Inverter MODBUS RTU Driver • 1:1 Connection Display side External Device side D-Sub 9pin (plug) TM2 Terminal Block Termination Signal name Signal name Shield resistance 200Ω LINE(+) Display LINE(-) GND(SG) RS(RTS) Shell • 1:n Connection Display side External Device side External Device side D-Sub 9pin (plug) TM2 Terminal Block...
  • Page 41: Supported Devices

    Click the parameter to use and press "Select", then the address is entered. • If you select the [Set as Default Value] option, the set value for a new address entry will be displayed as the default value. X200 series This address can be specified as system data area. Device...
  • Page 42 Inverter MODBUS RTU Driver SJ700 series This address can be specified as system data area. Device Bit Address Word Address 32bits Notes Coil 00001 - 0004E 00001 - 00031 Holding register 40001 - 43507 Specify only the word address whose last digit is "1". •...
  • Page 43 Inverter MODBUS RTU Driver SJ200 series This address can be specified as system data area. Device Bit Address Word Address 32bits Notes Coil 00000 - 0001F 00000 - 00010 Holding register 40000 - 40900 • Holding register number 0900h is an address for the command (enter command) to write in nonvolatile memory.
  • Page 44 Inverter MODBUS RTU Driver WJ200 series This address can be specified as system data area. Device Bit Address Word Address 32bits Notes Coil 00001 - 00058 00001 - 00041 Holding register 40001 - 4252D For word addresses, only specify addresses with "1" as the last digit. •...
  • Page 45: Device Code And Address Code

    Inverter MODBUS RTU Driver Device Code and Address Code Use device codes and address codes when you set "Device Type & Address" for the address type of the data display or other devices. X200 series Device Code Device Device Name...
  • Page 46 Inverter MODBUS RTU Driver WJ200 series Device Code Device Device Name Address Code (HEX) Coil 0080 Value of (word address -1) divided by 0x10 Holding register 0000 Value of (word address - 1) GP-Pro EX Device/PLC Connection Manual...
  • Page 47: Error Messages

    • Attempted to write in a register during tripping (UV). • Attempted to write in a register with software lock enabled. Attempted to write in a register with software lock enabled. The error code is supported by X200 series and WJ200 series only. GP-Pro EX Device/PLC Connection Manual...

This manual is also suitable for:

Sj700-2 seriesSj200 seriesL200 seriesWj200 series