Hitachi WJ Series User Manual page 399

Table of Contents

Advertisement

Chapter 15
S14: DC braking does not work
!
Estimated cause (s) ▶
DC braking force, DC
braking time, etc. are not
set or incorrect.
"External DC braking [DB]"
is not assigned to the input
terminal function. Or, the
wiring is wrong.
S15: Noise is generated in TV, radio or devices near the inverter
!
Estimated cause (s) ▶
Conductive/radiation noise
from the inverter
S16: Cannot be operated/set by communication option board
!
Estimated cause (s) ▶
RUN command input
source selection or
frequency input source
selection is not "Option"
S17: Cannot connect to the inverter configuration software ProDriveNext
!
Estimated cause (s) ▶
The communication cable
is broken or wrong.
*1. "2nd-motor control [SET]" target parameter. Replace with the 2nd-control parameter if necessary.
Exemplar measures to be taken
Check the settings of DC braking related parameters [A051] to
[A058].
When activating DC braking by input terminal, confirm that
"External DC braking [DB]" is assigned together with the above
setting. Also check the wiring of the [DB] input terminal.
Exemplar measures to be taken
Locate the inverter wires as far as possible from nearby
devices, TVs, radios, etc.
Install a radio noise filter (zero-phase reactor (ZCL)) to the
power input/output of the inverter.
Exemplar measures to be taken
Check that "Frequency input source selection [A001]" and
"RUN command input source selection [A002]
"Option".
Exemplar measures to be taken
Check that there is no disconnection or contact failure at the
communication cable or connection terminal, or that the cable
specification is correct.