Chapter 16
16.1.1
Daily Inspection
Check that the following abnormalities are not observed during operation.
No.
1
Motor operation is not abnormal.
2
There is no abnormality in the environment where the device is installed.
3
There is no abnormality in the cooling system.
4
No abnormal vibration or sound is observed.
5
No abnormal overheat or discoloration is observed.
6
No abnormal smell is observed.
While the inverter is running, check the input voltage of inverter using a multimeter, etc.
No.
1
There is no frequent occurrence of variation of power supply voltage.
2
Three-phase AC voltage keeps a good balance.
16.1.2
Cleaning
Keep the inverter in a clean condition.
No.
When cleaning the inverter, use a soft cloth soaked in neutral detergent to gently wipe up
1
the dirtied parts.
Do not use solvents such as acetone, benzene, toluene, or alcohol as they may melt the
2
surface or strip the coating of the inverter.
3
Do not use detergents or alcoholic cleaners to clean the keypad displays.
16.1.3
Periodic Inspection
Check sections that cannot be inspected unless operation is stopped and sections requiring
periodic inspection.
Please contact your supplier or local Hitachi inverter sales office for periodic inspection.
No.
1
Check that there is no abnormality in the cooling system and clean the air filter, etc.
Check the tightness and retighten if necessary.
2
Due to effects of vibration or temperature change, tightened portions of screws or bolts
may loosen. Make sure to carefully check and perform the work.
3
No corrosion or damage is observed on the conductors and insulators.
4
Measurement of insulation resistance
5
Checking and replacing the cooling fan, smoothing capacitor, and relay
16.1.4
Periodic Function Test for Safety Function (STO)
When handling the WJ-C1 as a functional safety certified product, be sure to perform the
following items. For details, refer to the separate volume "WJ series C1 Safety Function Guide
(NT3612*X)".
A periodical STO functional test must be performed at least once in a year to maintain the
intended safety performance level of the STO function. This periodical STO function test is one
of the conditions for the STO function of WJ-C1 to meet PL e of ISO13849-1 and SIL 3 of
IEC61800-5-2.
Maintenance and Inspection
Description
Description
Description
Description
16-1-2
☑
□
□
□
□
□
□
☑
□
□
☑
□
□
□
☑
□
□
□
□
□