Outputting Monitor Data By Analog Output - Hitachi WJ Series User Manual

Table of Contents

Advertisement

Chapter 9
9.16.4

Outputting Monitor Data by Analog Output

 How to output the inverter monitor data externally by analog output?
Q
 The [Ao1] terminal is an analog voltage output terminal from 0 to 10 VDC. Output frequency and
A
output current can be monitored.
 Analog output may not be stable immediately after power-on or power interruption.
!
Code
[C028]
[Ao1] Output monitor selection
List of [Ao1] terminal output data ([C028] set values)
 The following lists the data that can be output from the [Ao1] terminal.
Data
00
Output frequency
01
Output current
02
Output torque
04
Output voltage
05
Input power
06
Electronic thermal load ratio
07
LAD frequency
10
Cooling fin temperature
11
Output torque (signed)
13
General-purpose analog YA(1)
16
Option
*1. "LAD frequency (07)" is the frequency commanded by the inverter and corresponds to "Output
frequency monitor [d001]". "Output frequency (00)" is a value that takes into account vector control
compensation and stabilization control such as sensorless vector control. "Output frequency" output
may appear unstable at low speeds during overload limit deceleration, etc. In this case, changing it to
"LAD frequency" results in a better stability.
*2. When "Speed feedback" is set for "Pulse input, target function selection [P003]", "Speed detection value
monitor [d008]" is outputted.
*3. Valid only when the control method is sensorless vector control.
*4. When "Frequency conversion gain [b086]" is set, a converted value is outputted for the digital output
frequency.
*5. For details on YA(1), refer to the "Easy-Sequence Function (EzSQ) Programming Guide (NT2021*X)".
*6. Specifications of output torque (signed) are as follows.
[Ao1] bias adjustment
[C109] = 50%
Item
Name
*1*2
*3
*1
*3*6
*5
[Ao1] gain adjustment
[Ao1] Output (VDC)
[C106] = 200%
10
5
0
0%
100%
Description
Selects data to be output from the
[Ao1] terminal.
Output full scale value
0 to the maximum frequency (Hz)
0 to 200 (%)
0 to 200 (%)
0 to 133 (%)
(e.g., Approx. 7.5 VDC at 200 V in 200 V class)
0 to 200 (%)
0 to 100 (%)
0 to the maximum frequency (Hz)
0 to 200 (°C) (0 output for temperatures below 0°C)
*6
0 to 200%
0 to 100%
- (currently no supported options)
[Ao1] gain adjustment
[C106] = 100%
0 to 200%
‐200 to 0%
Output torque (%)
200%
9-16-7
Inverter Functions
Data
00 to 16

Advertisement

Table of Contents
loading

Table of Contents