Chapter 8
When operating by inputting RUN command and frequency command from control terminal
(1) Before test run, confirm that each parameter is set correctly according to "8.1 Mandatory
Setting for Operation".
(2) Set [F001], [A001], [A002], [C001], and [C002] as shown in the table below.
It is recommended that "Output frequency setting or monitor [F001]" is set to a low speed of
approximately 10Hz for safety at the first time.
(3) Monitor the output frequency with [d001] and confirm that "0.00" (Hz) is displayed.
(4) Check with [F001] that the analogue voltage is 0VDC and the frequency command is 0.00
(Hz). When the forward [FW] input terminal or reverse [RV] input terminal is turned ON, the
running LED [RUN] of keypad lights.
(5) When the analogue voltage, which is a frequency command, is gradually increased, the motor
starts to rotate.
(6) Check there are any abnormalities in output frequency monitor, actual motor rotation speed,
motor rotation direction, and inverter. The motor rotation direction can be checked by
"Rotation direction monitor [d003]".
(7) After checking the operation, turn OFF the forward [FW] input terminal or reverse [RV] input
terminal. The motor starts decelerating and after stopping, the running LED [RUN] on keypad
turns off.
Code
Output frequency
[d001]
monitor
Rotation direction
[d003]
monitor
Output frequency
[F001]
setting or monitor
Acceleration time
[F002]
1 setting or
monitor, 1st-motor
Deceleration time
[F003]
1 setting or
monitor, 1st-motor
Frequency input
[A001]
source selection,
1st-motor
RUN command
input source
[A002]
selection, 1st-
motor
Control mode
[A044]
selection, 1st-
motor
Input terminal [1]
[C001]
function
Input terminal [2]
[C002]
function
Mandatory Setting for Motor Drive and Test Run
Item
Displays the output frequency of the
inverter.
Displays the operation direction of the
inverter.
When the frequency command source is
analogue voltage, it becomes frequency
command monitor.
Set the acceleration time and deceleration
time as necessary.
The default value is 10.0 (s).
The voltage input at the input terminal is
used as a frequency command.
Starts rotation by forward [FW]/reverse [RV]
of the input terminal.
Operates with the constant torque
characteristics of V/f control.
Assign "Forward [FW]".
Assign "Reverse [RV]".
8-2-3
Description
Data
0.0 to
Maximum frequency
F (forward)/ r (reverse)/
o (stop)
0.0, Minimum frequency
to Maximum frequency
0.00 to 3600.00 (s)
01
01
00
00
01