Setting Frequency Command On Frequency Monitor - Hitachi WJ Series User Manual

Table of Contents

Advertisement

Chapter 9
9.2.15

Setting Frequency Command on Frequency Monitor

 How to adjust the frequency command by the keypad while monitoring the output frequency on
Q
the keypad?
 When the "Enable frequency changes through monitor display [b163]" is set to "Enable (01)" and
A
the "Frequency command selection [A001]
command can be changed by pressing keys on the keypad while "Output frequency monitor
[d001]" or "Output frequency scale conversion monitor [d007]" is displayed as long as the
inverter is running.
 After changing the frequency command, pressing the [SET] key saves the new frequency
command value in the inverter memory.
Code
Output frequency
[d001]
monitor
Output frequency scale
[d007]
conversion monitor
Enable frequency
[b163]
changes through
monitor display
 Please note that if the "FUP/FDN data save enable [C101]" is set to "Save (01)", the frequency
!
command value that was changed using [d001]/[d007] is saved in the inverter memory when
the power is shut off.
 This function cannot be used during PID operation or when the inverter is stopped.
 Since this function overwrites the "Output frequency setting or monitor [F001]" setting while
displaying [d001]/[d007], there may be a time discrepancy between the key operation and the
display depending on the acceleration/deceleration time setting.
*1. "2nd-motor control [SET]" target parameter. The second control parameter is also subject to setting.
*2. For details, refer to "10.1.1 Monitor the Output Frequency".
*1
Item
Displays the current output frequency.
Displays the value of [d001] × [b086]
Disabled:
The frequency command cannot be changed
by [d001]/[d007].
Enabled:
The frequency command can be changed by
[d001]/[d007].
9-2-22
" is set to "Parameter setting (02)", the frequency
Description
Inverter Functions
Data
0.00 to
590.00 (Hz)
0.00 to
*2
.
58994.10
00
01

Advertisement