Chapter 9
9.12.4
Outputting a Signal When Inverter Is Ready to Run
How can I inform the system that the inverter is ready to operate with a RUN command?
Q
Assigning "Inverter ready [IRDY] (50)" to one of the output terminal functions
A
([C021]/[C022]/[C026]) enables the inverter to output an inverter ready signal.
The [IRDY] signal is output when the inverter is ready to accept a RUN command.
The system does not function even if RUN commands are input if this signal has not been
!
output.
This signal remains off while output is unavailable, such as during startup preparations when
turning the power on, undervoltage, tripping, a free-run stop command is issued, STO is
activated, and other circumstances.
Code
[C021]
[C022]
Output terminal function
[C026]
Reset
[RS] input
Alarm
[AL] output
Inverter ready
[IRDY] output
Item
Inverter ready [IRDY]:
This signal is output when the inverter is ready
to accept RUN commands.
ON
ON
9-12-4
Inverter Functions
Description
ON
ON
Data
50