Chapter 1
Field wiring conductor size and torque values making for wiring terminal
Model
C1-001S
C1-002S
C1-004S
C1-007S
C1-015S
C1-022S
C1-001L
C1-002L
C1-004L
C1-007L
C1-015L
C1-022L
C1-037L
C1-055L
C1-075L
C1-110L
C1-150L
C1-004H
C1-007H
C1-015H
C1-022H
C1-030H
C1-040H
C1-055H
C1-075H
C1-110H
C1-150H
Temperature rating of field wiring installed conductor:
 For models C1-001S, C1-002S, C1-004S, C1-007S, C1-015S, C1-001L, C1-004L, C1-007L,
C1-015L, C1-004H, C1-007H, C1-015H, C1-022H, C1-030H and C1-040H
 Except above models - 75 degree C only.
Field wiring Terminal marking for wire type:
 Use copper conductors only
Required Torque
Screw Size
M3.5
M3.5
M3.5
M4
M4
M4
M3.5
M3.5
M3.5
M3.5
M4
M4
M4
M5
M5
M6
M8
M4
M4
M4
M4
M4
M4
M5
M5
M6
M6
- 60 degree C only.
1-4-2
Safety Instructions/Risks
(N・m)
1.0
1.0
1.0
1.4
1.4
1.4
1.0
1.0
1.0
1.0
1.4
1.4
1.4
3.0
3.0
3.9 to 5.1
5.9 to 8.8
1.4
1.4
1.4
1.4
1.4
1.4
3.0
3.0
3.9 to 5.1
3.9 to 5.1
Wire Rang
2
(AWG/mm
)
AWG16 (1.3 mm
2
)
2
AWG16 (1.3 mm
)
AWG16 (1.3 mm
2
)
2
AWG12 (3.3 mm
)
2
AWG10 (5.3 mm
)
2
AWG10 (5.3 mm
)
2
AWG16 (1.3 mm
)
2
AWG16 (1.3 mm
)
2
AWG16 (1.3 mm
)
2
AWG16 (1.3 mm
)
2
AWG14 (2.1 mm
)
2
AWG12 (3.3 mm
)
AWG10 (5.3 mm
2
)
2
AWG6 (13 mm
)
AWG6 (13 mm
2
)
2
AWG4 (21 mm
)
2
AWG2 (34 mm
)
2
AWG16 (1.3 mm
)
2
AWG16 (1.3 mm
)
AWG16 (1.3 mm
2
)
2
AWG14 (2.1 mm
)
2
AWG14 (2.1 mm
)
2
AWG12 (3.3 mm
)
2
AWG10 (5.3 mm
)
AWG10 (5.3 mm
2
)
2
AWG6 (13 mm
)
AWG6 (13 mm
2
)