Chapter 18
Code
Name
00: Output frequency
01: Output current
02: Output Torque
04: Output voltage
05: Input power
[Ao1] Output
06: Electronic thermal load
monitor selection
C028
(Analog output
07: LAD frequency
monitor)
10: Cooling fin temperature
11: Output torque (signed)
13: EzSQ General-purpose
16: Option
(0.20 to 2.00) × Rated
[Ao2] Output
current (A)
reference value
C030
(When [C027] is set to "Digital
(at digital output
current monitor", set the current to
current monitor)
be output at 1440Hz.)
Output terminal
C031
[11] active state
Output terminal
00: NO: Normally Open
C032
[12] active state
01: NC: Normally Closed
Output terminal
C036
[AL] active state
Low current
00: Enable during running
C038
signal output
01: Enable only during
mode selection
constant speed
Low current
(0.00 to 2.00) × Rated
C039
detection level
current (A)
Overload signal
00: Enable during running
C040
output mode
01: Enable only during
selection
Overload warning
C041
level, 1st-motor
(0.0 to 2.00) × Rated current
(A)
Overload warning
C241
level, 2nd-motor
Arrival frequency
C042
during
0.00 to 590.00 (Hz)
acceleration
Arrival frequency
C043
during
0.00 to 590.00 (Hz)
deceleration
PID over
C044
0.0 to 100.0 (%)
deviation level
Arrival frequency
C045
2 during
0.00 to 590.00 (Hz)
acceleration
Arrival frequency
C046
2 during
0.00 to 590.00 (Hz)
deceleration
Pulse input/
monitor output
C047
0.01 to 99.99
scale convert
gain
Turn-off level for
C052
the PID feedback
0.0 to 100.0 (%)
compare signal
Turn-on level for
C053
the PID feedback
0.0 to 100.0 (%)
compare signal
Over/ Under-
00: Over-torque
C054
torque selection
01: Under-torque
*2. 100% of the set value means the rated current of the WJ-C1.
List of Parameters/Modbus Coil/Register Numbers
Data range
(Sensorless vector control)
ratio
(Sensorless vector control)
analog output YA1
constant speed
18-2-20
Change
Initial
Set
during
value
value
Register No.
running
07
✓
141Ch
Rated
✓
141Eh
current
00
✓
141Fh
00
✓
1420h
01
✓
1424h
01
✓
1426h
Rated
✓
1427h
current
01
✓
1428h
Rated
current
✓
1429h
× 1.15
Rated
current
✓
2429h
× 1.15
142Ah (High)
0.00
✓
142Bh (Low)
142Ch (High)
0.00
✓
142Dh (Low)
3.0
✓
142Eh
142Fh (High)
0.00
✓
1430h (Low)
1431h (High)
0.00
✓
1432h (Low)
1.00
✓
1433h
100.0
✓
1438h
0.0
✓
1439h
00
✓
143Ah
Modbus communication
Data Range
Resolution
0 to 2, 4 to 7,
10,
-
11, 13, 16
200 to 2000 (ND)
0.1
200 to 1500 (LD)
(%)
-
0 to 1
-
-
0 to 1
-
0.1
0 to 2000
(%)
0 to 1
-
0.1
(%)
0 to 2000
0.1
(%)
0 to 59000
0.01
0 to 59000
0.01
0 to 1000
0.1
0 to 59000
0.01
0 to 59000
0.01
1 to 9999
-
0 to 1000
0.1
0 to 1000
0.1
0 to 1
-
Page
9-16-7
9-16-6
*2
9-16-1
9-11-4
*2
9-11-3
*2
*2
9-13-2
9-13-3
9-8-2
9-13-2
9-13-3
9-16-6
9-8-2
9-6-4