Chapter 18
Code
Name
EzCOM start
00: [ECOM] terminal
C100
method selection
01: Always communication
FUP/FDN data
00: Not save
C101
save enable
01: Save
00: Reset at turn-ON
01: Reset at turn-OFF
02: Only enable in trip status
Reset mode
C102
selection
03: Only enable in trip status
00: Restart from 0 Hz
01: Restart with frequency
Restart mode
C103
after RS release
02: Active frequency matching
FUP/FDN [UDC]
00: 0Hz
C104
terminal mode
01: Stored data (stored by
selection
[Ao2] gain
C105
50 to 200 (%)
adjustment
[Ao1] gain
C106
50 to 200 (%)
adjustment
[Ao1] bias
C109
0 to 100 (%)
adjustment
Overload warning
(0.00 to 2.00) × Rated
C111
level 2
current (A)
C117 JOG sensitivity
1 to 24
JOG carry
C118
1 to 100
sensitivity
Output terminal
C130
0.0 to 100.0 (s)
[11] on-delay time
Output terminal
C131
0.0 to 100.0 (s)
[11] off-delay time
Output terminal
C132
0.0 to 100.0 (s)
[12] on-delay time
Output terminal
C133
0.0 to 100.0 (s)
[12] off-delay time
Output terminal
C140
0.0 to 100.0 (s)
[AL] on-delay time
Output terminal
C141
0.0 to 100.0 (s)
[AL] off-delay time
LOG1 operand-1
C142
Same as [C021]
selection
(Excluding [LOG1] to [LOG3],
LOG1 operand-2
[OPO], and no)
C143
selection
LOG1 logical
00: AND
C144
calculation
01: OR
selection
02: XOR
LOG2 operand-1
C145
Same as [C021]
selection
(Excluding [LOG1] to [LOG3],
LOG2 operand-2
C146
[OPO], and no)
selection
LOG2 logical
00: AND
C147
calculation
01: OR
selection
02: XOR
LOG3 operand-1
C148
Same as [C021]
selection
(Excluding [LOG1] to [LOG3],
LOG3 operand-2
C149
[OPO], and no)
selection
LOG3 logical
00: AND
C150
calculation
01: OR
selection
02: XOR
Input terminal [1]
C160
0 to 200 (× 2ms)
response time
Input terminal [2]
C161
0 to 200 (× 2ms)
response time
Input terminal [3]
C162
0 to 200 (× 2ms)
response time
List of Parameters/Modbus Coil/Register Numbers
Data range
(Trip release at turn-ON)
(Trip release at turn-ON,
clear only trip memory)
matching
restart
[C101]=01)
18-2-22
Change
Initial
Set
during
value
value
Register No.
running
00
×
1468h
00
✓
1469h
00
✓
146Ah
00
✓
146Bh
00
✓
146Ch
100
✓
146Dh
100
✓
146Eh
0
✓
1471h
Rated
current
✓
1473h
× 1.15
1
×
1479h
20
×
147Ah
0.0
✓
1486h
0.0
✓
1487h
0.0
✓
1488h
0.0
✓
1489h
0.0
✓
1490h
0.0
✓
1491h
00
✓
1492h
00
✓
1493h
00
✓
1494h
00
✓
1495h
00
✓
1496h
00
✓
1497h
00
✓
1498h
00
✓
1499h
00
✓
149Ah
1
✓
14A4h
1
✓
14A5h
1
✓
14A6h
Modbus communication
Data Range
Resolution
0 to 1
-
0 to 1
-
0 to 3
-
0 to 2
-
0 to 1
-
50 to 200
1
50 to 200
1
0 to 100
1
0 to 2000
0.1
1 to 24
1
1 to 100
1
0 to 1000
0.1
0 to 1000
0.1
0 to 1000
0.1
0 to 1000
0.1
0 to 1000
0.1
0 to 1000
0.1
Same as
-
[C021]
(Excluding 33
-
to 35, 63,255)
0 to 2
-
Same as
-
[C021]
(Excluding 33
-
to 35, 63,255)
0 to 2
-
Same as
-
[C021]
(Excluding 33
-
to 35, 63,255)
0 to 2
-
0 to 200
2
0 to 200
2
0 to 200
2
Page
11-4-2
9-2-18
9-1-9
9-7-8
9-2-18
9-16-6
9-16-8
9-11-3
7-1-6
9-16-4
9-13-5
9-15-3