Chapter 9

9.16 Functions with External Signal Output

9.16.1

Using External I/O Output Signal Functions

 How to detect warning, error, and status signals emitted by the inverter with an external system?
Q
 Output terminals [11], [12], [AL0]-[AL1]/[AL0]-[AL2] are intelligent output terminals. By assigning
A
the functions in the list of output terminal functions shown on the next page to [C021], [C022],
and [C026], the specified functions can be assigned to the corresponding output terminals.
 The output terminals [11], [12], [AL0]-[AL1]/[AL0]-[AL2] can be individually selected as "a"
contact (NO) input or "b" contact (NC) input by setting [C031], [C032], and [C036].
 The output terminals [11] and [12] are open collector outputs, and the output terminals [AL0]-
[AL1]/[AL0]-[AL2] are "c" contact relay outputs.
 When using a "c" contact relay, check the power supply status and the open/close status of the
!
relay output terminals.
Code
[C021]
Output terminal
[C022]
function
[C026]
[C031]
Output terminal
[C032]
active state
[C036]
Open collector output terminal specifications
Output terminal
[11]
[12]
[CM2]
Output terminal active
state
00
(NO: Normally Open)
01
(NC: Normally Closed)
Open collector output
terminal (inside the inverter)
12
CM2
[RUN]
Item
Assigns output terminal functions to the output
terminals [11], [12], [AL0] to [AL1]/[AL0] to [AL2].
The settings of [C021], [C022], and [C026]
correspond to the output terminals, respectively.
Operates as "a" contact (NO).
Operates as "b" contact (NC).
Electrical characteristics
Voltage decreases when ON: 4 VDC or less
Allowable maximum voltage: 27 VDC
Allowable maximum current: 50 mA
Common terminal of [11] and [12]
Allowable maximum current: 100 mA
Power
state
ON
OFF
ON
OFF
* Terminal names such as [FW] under the
terminal numbers are initial assigned
functions when "Initialize data selection
[b085]" set to "Pattern 0 (00)". For details
of initial setting when [b085] is set to
other value, refer to "18.2.5 C Parameter
11
[FA1]
Group".
Description
Terminal function
Open collector operation
output
ON
OFF
-
ON
OFF
-
9-16-1
Inverter Functions
Data
Refer to the list of
output terminal
functions on the next
page.
00
01
Closed
Open
-
Open
Closed
-