Chapter 18
Code
Name
00: Disable
Overcurrent
01: Enable (without voltage
b027
suppression
reduction)
enable
02: Enable (with voltage
reduction)
(0.20 to 2.00) × Rated
Active frequency
current (A) (Normal duty (ND))
b028
matching restart
(0.20 to 1.50) × Rated
level
current (A) (Low duty (LD))
Active frequency
b029
matching restart
0.1 to 3000.0 (s)
constant (speed)
00: Output frequency at shut
Active frequency
b030
matching restart
01: Maximum frequency
speed selection
02: Setting frequency
00: [SFT] terminal (locked
01: [SFT] terminal (locked
Soft-Lock
b031
selection
02: Locked except [b031]
03: Locked except [b031] and
Motor cable
b033
length code
5 to 20
selection
Accum. RUN time
(RNT) / Accum.
b034
0 to 65535 (× 10hr)
power-on time
(ONT)
RUN direction
00: No restriction
b035
restriction
01: Only forward
selection
02: Only reverse
Reduced voltage
0 (short time) to 255 (long
b036
start time
time)
00: Full display
Display
01: Function-specific display
b037
restriction
02: User settings and [b037]
selection
03: Data comparison display
05: Monitor only
000: Parameter that SET-key
Initial display
001 to 060: d001 to d060
b038
selection
201: F001
202: Monitor B display of
User-parameter
00: Disable
b039
automatic setting
01: Enable
function enable
00: 4 quadrant individual
Torque limit
01: Switched by terminal
b040
selection
02: [Ai1] terminal input
03: Option
Torque limit 1
b041
0 to 200 (%) / no: Disable
(Forward drive)
Torque limit 2
b042
(Reverse
0 to 200 (%) / no: Disable
regenerative)
Torque limit 3
b043
0 to 200 (%) / no: Disable
(Reverse drive)
Torque limit 4
b044
(Forward
0 to 200 (%) / no: Disable
regenerative)
*1. 100% of the set value means the rated current of the WJ-C1.
*2. The default settings when initialize by setting 00/01/03 to "Initialize data selection [b085]".
List of Parameters/Modbus Coil/Register Numbers
Data range
down
except [b031])
except [b031] and
frequency settings)
frequency settings
was pressed last
WOP
setting
[TRQ1]/[TRQ2]
18-2-13
Change
Initial
Set
during
value
value
Register No.
running
01/
00/
131Ch
*2
01
Rated
131Dh
current
0.50
131Eh
00
131Fh
01
1320h
10
1322h
1323h (High)
0
1324h (Low)
00
×
1325h
2
1326h
00
1327h
001
1328h
00
1329h
00
132Ah
200
132Bh
200
132Ch
200
132Dh
200
132Eh
Modbus communication
Data Range
Resolution
0 to 2
-
200 to 2000 (ND)
0.1
200 to 1500 (LD)
(%)
1 to 30000
0.1
0 to 2
-
0 to 3
* Writing 10 is
invalid and no
-
communication
error.
5 to 20
1
0 to 65535
10hr 9-11-9
0 to 2
-
0 to 255
-
0 to 5
* Writing 4 is
invalid and no
-
communication
error.
000 to 202
-
0 to 1
-
0 to 3
-
0 to 200/
1
255(no)
0 to 200/
1
255(no)
0 to 200/
1
255(no)
0 to 200/
1
255(no)
Page
9-9-3
*1
9-7-4
7-2-5
8-1-14
9-4-2
9-7-1
7-2-1
7-2-8
7-2-9
9-6-2
9-6-2