Modbus Holding Registers - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

B−26

ModBus Holding Registers

The following tables list the holding registers for the inverter interface to the network.
The table legend is given below.
• Function Code - The inverter's reference code for the parameter or function (same as
inverter keypad display)
• Name - The standard functional name of the parameter or function for the inverter
• R/W - The read-only(R) or read-write access(R/W) permitted to the data in the
inverter
• Description - How the parameter or setting works (same as Chapter 3 description).
• Reg. - The network
high-byte and low-byte address.
• Range - The numerical range for the network value that is sent and/or received
TIP: The network values are binary integers. Since these values cannot have an
embedded decimal point, for many parameters it represents the actual value (in
engineering units) multiplied by a factor of 10 or 100. Network communications must
use the listed range for network data. The inverter automatically divides received
values by the appropriate factor in order to establish the decimal point for internal use.
Likewise, the network host computer must apply the same factor when it needs to work
in engineering units. However, when sending data to the inverter, the network host
computer must scale values to the integer range listed for network communications.
• Resolution - This is the quantity represented by the LSB of the network value, in
engineering units. When the network data range is greater than the inverter's
internal data range, this 1-bit resolution will be fractional.
Register No.
Function name
0000h
unused
0001h
Frequency source
0002h
0003h
Inverter status A
0004h
Inverter status B
0005h
Inverter status C
0006h
PID feedback
0007h
to
(Reserved)
0010h
register address offset
Function code
R/W
-
-
Inaccessible
F001 (high)
R/W
0 to 40000 (valid when A001 = 03)
F001 (low)
R/W
0: Initial status
2: Stopping
-
R
3: Running
4: Free-run stop
5: Jogging
-
R
0: Stopping, 1: Running, 2: Tripping
0: ---
1: Stopping
2: Decelerating
3: Constant-speed
-
R
4: Accelerating
5: Forward rotation
-
R/W
0 to 10000
-
R
-
for the value. Some values have a
Monitoring and setting items
6: DC braking
7: Retrying
8: Tripping
9: Undervoltage
(UV),
6: Reverse rotation
7: Switching from
fwd.
to rev. rotation,
operation
8: Switching from
rev.
to fwd. rotation,
9: Starting fwd.
10: Starting rev.
Data
resolution
0.01 [Hz]
-
-
-
0.01 [%]
-