Chapter 11
When reading the status of 16 consecutive coils from coil number 0001h, the order of the data
is as follows. Data 1 is byte data transmitted first.
Data 1
Data 2
If the read coil extends beyond the range of the defined coil number, coil data outside the range
is sent as "0".
If the command cannot be executed successfully, an exceptional response is returned. For
details, refer to "11.2.9 Exceptional Responses".
Reads coil numbers 0010h to 0058h can also be substituted by holding register reads register
number 1E01h to 1E05h. As an example, the bit-structure of the holding register 1E01h is
shown below. For details, refer to "18.1.1 List of Modbus Coil Numbers".
■
(Example) Bit-structure of holding register 1 E 01 h
(Holding register allocation status of coil number 0010h to 001Fh)
bit
Symbol
15
ONT
14
RNT
13
TRQ
12
UV
11
-
10
OTQ
9
FA3
8
AL
Bit7
Bit6
Bit5
0008h
0007h
0006h
0010h
000Fh
000Eh
Item
Accumulated power-on time
over
Accumulated operation time
over
Torque limited
Undervoltage
-
Over-torque/under-torque
Set frequency reached
Alarm
Bit4
Bit3
0005h
0004h
000Dh
000Ch
bit
Symbol
7
OD
6
OL
5
FA2
4
FA1
3
RUN
2
-
1
IRDY
0
Dir
11-2-2
RS485 Communication
Bit2
Bit1
Bit0
0003h
0002h
0001h
000Bh
000Ah
0009h
Item
Over deviation for PID control
Overload warning notice
Set frequency overreached
Constant-frequancy reached
Running
-
Inverter ready
Rotation direction (0: Forward/1:
Reverse)