Chapter 11
 When reading the status of 16 consecutive coils from coil number 0001h, the order of the data
is as follows. Data 1 is byte data transmitted first.
Data 1
Data 2
 If the read coil extends beyond the range of the defined coil number, coil data outside the range
is sent as "0".
 If the command cannot be executed successfully, an exceptional response is returned. For
details, refer to "11.2.9 Exceptional Responses".
 Reads coil numbers 0010h to 0058h can also be substituted by holding register reads register
number 1E01h to 1E05h. As an example, the bit-structure of the holding register 1E01h is
shown below. For details, refer to "18.1.1 List of Modbus Coil Numbers".
(Example) Bit-structure of holding register 1 E 01 h
(Holding register allocation status of coil number 0010h to 001Fh)
bit
Symbol
15
ONT
14
RNT
13
TRQ
12
UV
11
-
10
OTQ
9
FA3
8
AL
Bit7
Bit6
Bit5
0008h
0007h
0006h
0010h
000Fh
000Eh
Item
Accumulated power-on time
over
Accumulated operation time
over
Torque limited
Undervoltage
-
Over-torque/under-torque
Set frequency reached
Alarm
Bit4
Bit3
0005h
0004h
000Dh
000Ch
bit
Symbol
7
OD
6
OL
5
FA2
4
FA1
3
RUN
2
-
1
IRDY
0
Dir
11-2-2
RS485 Communication
Bit2
Bit1
Bit0
0003h
0002h
0001h
000Bh
000Ah
0009h
Item
Over deviation for PID control
Overload warning notice
Set frequency overreached
Constant-frequancy reached
Running
-
Inverter ready
Rotation direction (0: Forward/1:
Reverse)