■Normally completed e-mail count (Un\G5002)
The total number of times the high speed data logger module transfers an e-mail to the mail server is stored.
■Attachment transmission count (Un\G5003)
The total number of times the high speed data logger module transmits an e-mail with an attached file is saved.
■Abnormally completed e-mail count (Un\G5004)
The total number of times of communication error which are returned when e-mail transmission is required to the mail server
is stored.
About e-mail sending counts
• When e-mails are sent to all valid addresses: Transmission count is added up and stored in 'normally
completed e-mail count' (Un\G5002).
• When e-mails are sent to some invalid addresses: Transmission count is added up and stored in
'abnormally completed e-mail count' (Un\G5004).
• When e-mails are sent to all invalid addresses: Transmission count is added up and stored in 'abnormally
completed e-mail count' (Un\G5004).
However, depending on the mail server specifications, there may be situations where the transmission count
is not added up to 'abnormally completed e-mail count' (Un\G5004) even if an e-mail is sent to an invalid
address.
■Error log write count (Un\G5005)
The total number of times an error log is registered in the error log area is stored.
The error code is stored when 'E-mail transmission error' (X17) is ON.
■Error log write pointer (Un\G5006)
The error log number where the latest error log is registered is stored. (For example, when '16' is stored, it indicates that the
latest error log is registered in the area of the error log '16'.)
0: No error (No registration of error log)
1 or more: The error log number where the latest error log is registered
When 17 or more errors occur, error logs are registered again from error log 1 area.
■Error log 1 to 16 (Un\G5007 to 5342)
The error log when e-mail transmission is abnormally completed is stored.
Error log area is comprised of 16 error logs with the same data configuration.
Un\G5007 to 5027
Error log 1
Error log 2
Un\G5028 to 5048
Error log 16
Un\G5322 to 5342
● Error code
The error code is stored.
● To
The target e-mail address No. of the email where an error occurs on the communication with the mail server is stored.
The target e-mail address No. is set in the "Target e-mail address setting" in the e-mail setting.
● Subject
15 words from the beginning of the Subject in an e-mail is stored.
● Date
The time when an e-mail is sent is stored in BCD code.
b15
+0
+1
+2
+16
+17
Month (01H to 12H)
Hour (00H to 23H)
+18
+19
Second (00H to 59H)
Year (00H to 99H) first 2 digits
+20
b8
b7
Error code
TO
Subject (15 words)
Year (00H to 99H) last 2 digits
Day (01H to 31H)
Minute (00H to 59H)
Day of the week (0H to 6H)
Appendix 3 Buffer Memory
A
b0
Date
APPX