Report creation status area (Un\G4000 to 4989)
The status related to the report creation function can be checked in this area.
Buffer memory name
Report setting information
Report creation execution information
Report creation error information
Number of saved files exceeded
information
Report creation
Error code
information 1
Number of
newest folder
Number of
newest file
High speed
sampling failure
count
Processing
overload count
Unprocessed
buffer size
Unprocessed
data count
(current)
Unprocessed
data count
(maximum)
Creation trigger
detection count
Creation trigger
reoccurrence
count
Report creation
time (newest)
Report creation
time (maximum)
Report creation information 2 to 64
■Report setting information (Un\G4000 to 4003)
The setting status of a report setting is stored.
The bit corresponding to the configured report setting turns ON.
0: Unset
1: Set
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Un\G4000
16
15
14
13
Un\G4001
32
31
30
29
Un\G4002
48
47
46
45
Un\G4003
64
63
62
61
APPX
324
Appendix 3 Buffer Memory
Address
Un\G4000 to 4003
Un\G4008 to 4011
Un\G4012 to 4015
Un\G4016 to 4019
Un\G4030
Un\G4031 to 4032
Un\G4033 to 4034
Un\G4035
Un\G4036
Un\G4037
Un\G4038
Un\G4039
Un\G4040
Un\G4041
Un\G4042
Un\G4043
Un\G4045 to 4989
12
11
10
9
8
7
6
5
4
28
27
26
25
24
23
22
21
20
44
43
42
41
40
39
38
37
36
60
59
58
57
56
55
54
53
52
Description
The bit corresponding to the configured report setting turns ON.
The bit corresponding to the report setting that executes report creation turns ON.
The bit corresponding to the report setting where an report creation error is occurring turns
ON.
The information indicating the number of saved files is exceeding the set number of files is
stored.
An error code is stored in the area corresponding to the report setting where the report
creation error is occurring.
0: Normal
Other: Error code
The number of latest folders is stored.
The number of latest files is stored.
The total number of times the buffer is full is stored.
The number of times that the report creation processing did not catch up with the data
sampling processing is stored.
The buffer size to temporarily accumulate sampled data is stored.
The current number of units of data accumulated in the unprocessed buffer is stored.
The maximum number of units of data accumulated in the unprocessed buffer is stored.
The number of creation trigger occurrences detected is stored.
After a creation trigger, 'Creation trigger reoccurrence count' stores the number of creation
triggers that occur again during report creation.
(The number of creation triggers is not stored when "At the data logging file switching" is set
in the conditions of the creation trigger.)
The time required to create the latest report is stored in seconds unit.
The maximum value of time required to create a report is stored in seconds unit.
Details are the same as report creation information 1.
3
2
1
19
18
17
35
34
33
51
50
49

Advertisement