Error code
Error name
24E0H
System bus error
3000H
Period of time setting error
3001H
Trigger condition (the number of
times) setting error
3002H to 3003H
Scaling setting error
3004H
Data condition setting error
3005H
Compound condition (trigger
logging) setting error
3006H to 3007H
Compound condition (event
logging) setting error
3008H
Data condition setting error
3009H to 300CH
Setting file error
300DH
Trigger condition setting error
300EH to 3011H
Data condition setting error
3012H to 3013H
Setting file error
3014H
File switching setting error
3015H
Module error
3016H
Setting file error
3017H to 301EH
Module error
301FH
Unicode text output format
setting error
4 TROUBLESHOOTING
284
4.4 Error Code List
Error description
An error has been detected on the system bus.
An invalid setting has been made in the period
setting.
Or the setting file is corrupted.
An invalid count condition has been set for the
count trigger of trigger type in the trigger logging
setting.
Or the setting file is corrupted.
An invalid setting has been made in the scaling
setting.
Or the setting file is corrupted.
An invalid setting has been made in the data
condition setting.
Or the setting file is corrupted.
An invalid setting has been made in the trigger
compound condition setting of the trigger logging
setting.
Or the setting file is corrupted.
An invalid setting has been made in the trigger
compound condition settings of the "Event logging
setting".
Or the setting file is corrupted.
An invalid setting has been made in the data
condition setting.
Or the setting file is corrupted.
There is no setting file.
Or the setting file is corrupted.
An invalid setting has been made in the trigger
condition setting of the trigger logging setting.
Or the setting file is corrupted.
An invalid setting has been made in the data
condition setting.
Or the setting file is corrupted.
There is no setting file.
Or the setting file is corrupted.
An invalid file switch timing has been set in the file
switch setting.
Or the setting file is corrupted.
A module error has been detected.
There is no setting file.
Or the setting file is corrupted.
A module error has been detected.
An invalid Unicode text output format has been
set.
Or the setting file is corrupted.
Corrective action
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in the CPU module, or base
unit. Please consult your local Mitsubishi
representative.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.