Mitsubishi Electric MELSEC iQ-R Series User Manual page 272

High speed data logger module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error name
1AC8H to 1AD4H
Access target CPU
communication error
1AD5H
Channel number error
1AD6H to 1AE4H
Access target CPU
communication error
1AE5H
Routing parameter error
1AE6H
Access target CPU
communication error
1AE7H
Access target CPU
communication error
1AE8H to 1AFFH
Access target CPU
communication error
1B03H
FTP file transfer error
1B04H
No FTP transfer file error
1B05H
Shared folder transfer error
1B06H
No shared folder transfer error
1B07H
FTP server control port
connection error
1B08H
FTP server control port
disconnection error
4 TROUBLESHOOTING
270
4.4 Error Code List
Error description
Failed to communicate with access target CPU.
The RUN write setting of the Ethernet module is
disabled.
Failed to communicate with access target CPU.
No routing parameter has been set.
Failed to communicate with access target CPU.
Failed to communicate with access target CPU.
Failed to communicate with access target CPU.
• An error occurred during the FTP file transfer.
• The saved file was deleted before FTP transfer
because of file switching.
• Failed to execute the shared folder transfer.
• The saved file was deleted before shared folder
transfer because of file switching.
Failed to connect to the FTP server's control port.
Failed to disconnect from the FTP server's control
port.
Corrective action
• Correct "Access target CPU setting".
• Check the communication cable status and
access target CPU status.
• Adjust the response monitoring time setting.
• Check if the control CPU of the network module
on the network route to the access target CPU
is set to QCPU (Q mode).
• Check the routing parameter settings of the
CPU(s) on the access route.
• Check the network on the access route.
• Review the Ethernet module setting of the
access target CPU.
• Correct "Access target CPU setting".
• Check the communication cable status and
access target CPU status.
• Adjust the response monitoring time setting.
• Check if the control CPU of the network module
on the network route to the access target CPU
is set to QCPU (Q mode).
• Check the routing parameter settings of the
CPU(s) on the access route.
• Check the network on the access route.
• Set routing parameters on the access route.
• Check the CPU(s) on the access route.
• Check the network on the access route.
• When accessing via built-in Ethernet port,
check if UDP (MELSOFT Connection) is added
to the open setting of a built-in Ethernet port for
the access target CPU.
• Check the CPU(s) on the access route.
• Check the network on the access route.
• Correct "Access target CPU setting".
• Check the communication cable status and
access target CPU status.
• Adjust the response monitoring time setting.
• Check if the control CPU of the network module
on the network route to the access target CPU
is set to QCPU (Q mode).
• Check the routing parameter settings of the
CPU(s) on the access route.
• Check the network on the access route.
• Correct the file transfer settings.
• Check the connection status with the FTP
server.
• Check the destination FTP server status.
• Correct the saved settings (file switch timing,
number of saved files).
• Correct the saved settings (file switch timing,
number of saved files).
• Correct the file transfer settings.
• Check the connection status with shared folder.
• Check the destination shared folder status.
• Correct the saved settings (file switch timing,
number of saved files).
• Correct the saved settings (file switch timing,
number of saved files).
• Correct the file transfer settings.
• Check the network connection status with the
PING test.
• Check the destination FTP server status.
• When turning the power ON immediately after it
is turned OFF, wait a few minutes before turning
it ON.
• Check the connection status with the FTP
server.
• Check the destination FTP server status.