Precautions
• While the "Update settings" is being performed, all functions including the Data logging function, Event logging function,
and Report function stop.
■Event history
Display a list of errors/event histories which have occurred in the module.
Window
Click the [Event history file] button on the "Diagnostic" screen to diagnose the module.
Displayed items
Item
Displaying history/All history
Error/Event history list
[Event detail] button
[Clear history file] button
[Update] button
[Create CSV file] button
Display all history
Precautions
• After the module is started, the date and time of the events which occurred till the synchronization of time, is not registered,
and "-" is displayed.
• The event history is stored in the SD memory card. When the SD memory card is not inserted or the access status is
"Access stop", the event history is not recorded.
• Even if an error, among the errors (maximum 16) registered in the error history, occurs more than once, only one instance
will be displayed in the event history. The second and subsequent errors are not notified to the CPU module.
• Maximum 65536 records will be registered in the event history. When the number exceeds 65536, the old records will be
deleted sequentially.
Description
Displays history records being displayed and all history records in the SD memory card.
Displays a list of errors/event histories.
Displays "Error/Event detail" screen that displays details of the error/event being selected in the error/event history list.
Deletes the Error/Event history list.
Updates the latest Error/Event history list.
Saves the information of the Error/Event history file as a CSV file.
Information about error and event of the Error/Event history displayed is to be saved.
Select "Display all history" to save all the information.
Select this to display all the history data stored in the SD memory card.