Advertisement

Error code
Error name
196CH to 196FH
File read error
1970H to 1978H
File write error
1979H
Setting file error
197AH
Layout file read error
197DH
Layout file read error
197EH
File read error
1985H
Module error
1990H to 1997H
Report source file error
1999H to 199AH
Report file creation error
19B0H
Report source file error
19B1H to 19B5H
File open error
19B6H
Report source file error
19B7H to 19B8H
File read error
19BAH to 19BBH
File write error
4 TROUBLESHOOTING
266
4.4 Error Code List
Error description
Failed to read the file.
Failed to write the file.
The report layout file in the setting files is in
unsupported format.
Failed to read the layout file.
Failed to read the layout file.
Failed to read the file.
A module error has been detected.
Data logging file to be output to the report file
cannot be found.
An error occurred while creating a report file.
Data logging file to be output to the report file
cannot be found.
Failed to open the file.
Data logging file to be output to the report file
cannot be found.
Failed to read the file.
Failed to write the file.
Corrective action
• Check if the report layout file is edited with a
tool other than the Configuration Tool.
• Write the settings again with the Configuration
Tool.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Check if the report layout file is edited with a
tool other than the Configuration Tool.
• Configure the report layout settings with the
Configuration Tool and save the Excel file
again.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Configure and construct the system so that the
creation trigger occurs after the specified
number of records worth of data is saved in the
data logging file.
• Adjust the file switch timing for data logging.
• Check if the data logging file is being deleted
before the report is output.
• Replace the SD memory card.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Adjust the file switch timing for data logging.
• Check if the data logging file is being deleted
before the report is output.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Adjust the file switch timing for data logging.
• Check if the data logging file is being deleted
before the report is output.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.