Mitsubishi Electric MELSEC iQ-R Series User Manual page 282

High speed data logger module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error name
1F07H
Module error
1F13H
E-mail send queue full error
1F16H
E-mail send queue full error
1F19H to 1F1AH
Module error
1F1BH
File transfer queue full error
1F20H
File transfer failed
1F40H
Directory creation error
1F41H
File open error
1F46H
File write error
1F47H
CSV file write error
1F48H
Binary file write error
1F4AH
File write error
1F4BH
File open error
1F4CH to 1F4DH
Module error
1F51H
Setting file error
4 TROUBLESHOOTING
280
4.4 Error Code List
Error description
A module error has been detected.
The queue for sending e-mails is full.
The queue for sending e-mails is full.
A module error has been detected.
The queue for file transfers is full.
• An error occurred during the file transfer.
• The saved file to transfer was deleted before
the file transfer by file switching.
Failed to create the directory.
Failed to open the file.
Failed to write the file.
Failed to write the CSV file.
Failed to write the binary file.
Failed to write the file.
Failed to open the file.
A module error has been detected.
There is no setting file.
Or the setting file is corrupted.
Corrective action
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Lower the frequency that e-mails are sent.
• Decrease the settings that send e-mails.
• Lower the frequency of file switching.
• Check the communication cable status and
access target CPU status.
• Lower the frequency that e-mails are sent.
• Decrease the settings that send e-mails.
• Lower the frequency of file switching.
• Check the communication cable status and
access target CPU status.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Lower the frequency of file transfers.
• Decrease the settings with file transfers.
• Lower the frequency of file switching.
• Check the communication cable status and
access target CPU status.
• Correct the file transfer settings.
• Check the connection status with the FTP
server.
• Check the destination status.
• Correct the saved settings (file switch timing,
number of saved files).
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Delete unnecessary files on the SD memory
card to ensure free space.
• Replace the SD memory card.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.