E-mail setting

Set the settings required to use the e-mail service.
For details of the e-mail function, refer to the following:
Page 97 E-mail Function
Window
Click "Common setting" on the edit items tree, then click the [E-mail setting] button.
Displayed items
Item
Sender account setting
SMTP server name
E-mail address
SMTP port number
[Authentication setting] button
Target e-mail address setting
Destination group name
E-mail address
[Delete] button
[E-mail sending test] button
Optional setting
Resend when failed in sending
Resend buffer size
*1 The cell can be directly edited by selecting and double clicking the cell (or the pressing  key).
*2 The results of the e-mail transmission test are not reflected in the buffer memory and on the "E-mail transmission diagnostics" screen.
*3 If the network setting is changed, reset the CPU module after writing the settings, and then perform the e-mail transmission test.
Description
Set the SMTP server name with an IP address or a domain name. (Up to 64 characters)
Set the e-mail address for the high speed data logger module. (Up to 64 characters)
Specify the port number when accessing the SMTP server.
Displays the "Authentication setting" screen.
Page 140 Authentication setting
Set the group name for managing destinations as a group. (Up to 32 characters)
Set the destination e-mail addresses. (Up to 128 characters)
When specifying multiple destinations, separate them with comma (,).
Deletes the selected destination e-mail address setting.
Performs an e-mail transmission test to the selected destination group.
Select this to perform resend processing when an e-mail send failed.
The files to be resent are saved in the resend buffer in the SD memory card until the
resend is completed.
Specify the maximum size to be reserved for resend buffer.