Error code
Error name
1C0FH
Number of data error
1C10H
Number of data error
1C11H
Number of blocks error
1C12H
Number of blocks error
1C13H
Number of records error
1C14H
Record number error
1C15H
Number of records error
1C16H
Record attribute error
1C17H
Record attribute error
1C18H
Incorrect device value error
1C19H
Incorrect device value error
1C1AH
Incorrect device value error
1C1BH
Incorrect device value error
1C1CH
Incorrect device value error
1C1DH
Incorrect device value error
1C1EH
Incorrect device value error
1C1FH
Incorrect device value error
1C20H
Incorrect device value error
1C21H
Incorrect attribute error
1C22H
Incorrect attribute error
1C23H
Incorrect device value error
1C24H
Incorrect data type error
1C25H
No authority error
1C26H
SD memory card access error
1C27H
Module suspension error
1C28H
File size error
1C29H
Module suspension error
4 TROUBLESHOOTING
274
4.4 Error Code List
Error description
The total of specified recipe file data exceeded
256.
A value other than "1" is specified for the number
of bit device data.
Incorrect number of blocks is specified.
Insufficient number of blocks against specified
number of blocks.
Incorrect number of records is specified.
Record numbers are inconsecutive.
Or the same record numbers exist.
Insufficient number of records against specified
number of records.
An incorrect character is specified for the record
attribute.
Multiple attributes are specified for a specified
record.
Or an incorrect character is specified for the
record attribute.
A value out of the range is specified for the data
type "16bit BCD".
A value out of the range is specified for the data
type "32bit BCD".
A value out of the range is specified for the data
type "Bit".
A value out of the range is specified for the data
type "Double Word [Signed]".
A value out of the range is specified for the data
type "FLOAT [Double Precision]".
A value out of the range is specified for the data
type "Double Word [Unsigned]".
A value out of the range is specified for the data
type "Word [Signed]".
A value out of the range is specified for the data
type "FLOAT [Single Precision]".
A value out of the range is specified for the data
type "Word [Unsigned]".
The write process is performed on the record with
'P' attribute.
The read process is performed on the record with
'N' attribute.
A record number whose device value cell is blank
is specified.
"Bit" is specified for the data type of word device.
The recipe execution operation was performed by
a user who does not have a administrator's
authority.
The access to the SD memory card was
attempted when the file access was being
stopped.
The recipe execution operation was performed
when the module suspended error is being
occurred.
A recipe file whose file size is '0' is specified.
The recipe execution operation was performed
when the operation of high speed data logger
module was being suspended.
Corrective action
• Correct the recipe file to obtain the total of data
less than 256.
• Change the number of bit device data to "1".
• Specify a value within the range.
• Check the blocks and the number of blocks for
Recipe files.
• Specify a value within the range.
• Check the record numbers of the recipe file.
• Check the records and the number of records
for Recipe files.
• Check the record attribute for recipe file.
• Check the record attribute for recipe file.
• Specify a value within the range of '16bit BCD'
for the device value.
• Specify a value within the range of '32bit BCD'
for the device value.
• Specify 0 or 1 for the device value.
• Specify a value within the range of "Double
Word [Signed]" for the device value.
• Specify a value within the range of 'FLOAT
[double precision]' for the device value.
• Specify a value within the range of 'Double word
[unsigned]' for the device value.
• Specify a value within the range of 'Word
[signed]' for the device value.
• Specify a value within the range of 'FLOAT
[single precision]' for the device value.
• Specify a value within the range of "Word
[Unsigned]" for the device value.
• Check the specified record number.
• Check the specified recipe file name.
• Check the specified recipe file.
• Check the specified record number.
• Check the specified recipe file name.
• Check the specified recipe file.
• Check the device value of the specified record
number.
• Check the data type of the Recipe file.
• Retry with a user who has an administrator's
authority.
• Uncheck "Use the access authentication
function" in the Account setting.
• Check if a SD memory card is inserted.
• Execute "Access restart" and retry.
• Turn the clear file access stop request (Y3) ON,
and retry after the file access status (X2) is
turned OFF.
• Remove the module suspended error factor,
reset the CPU module, and retry.
• Check the specified recipe file.
• Change the operating status of the module to
"In operation".