Scaling
Set sampled device values to execute linear function transformation.
Operating procedure
1.
Click the [...] button for "Scaling" in the [Data] tab on the "Data logging setting" screen.
2.
Set "Operand 1", "Value 1", "Operand 2", and "Value 2" on the "Scaling" screen and click the [OK] button.
• When the data which is specified for scaling is used in other settings, the value after performing the scaling
conversion is applied to the data.
• For operation processing specified in the scaling, all values are calculated as double precision floating point
numbers.
The result is output with the specified output format.
• When the calculation result is over the maximum value or under the minimum value for the specified output
format range, the data to be output differs.
(Unicode text file, CSV file: Page 359 Data line)
(Binary file: Page 361 Binary file)
Output format
Specify the format (such as decimal format and exponential format) when the data is output to a file.
Operating procedure
1.
Click the [...] button for "Output format" in the [Data] tab on the "Data logging setting" screen.
2.
Specify the output format on the "Output format" screen and click the [OK] button.
Precautions
• When outputting data to a folder name or a file name
If Word [Signed], Double Word [Signed] is specified to the data type, the negative values may get output to the file name or
the folder name depending on the device value of the CPU module.
If a negative value is output, "-" will be added to the number of digits of zero padding even when the number of total digits is
specified in "zero-padding."
When fixing the file or folder name length, specify Word [Unsigned]/Bit String [16-bit], Double Word [Unsigned]/Bit String [32-
bit] and not Word [Signed] or Double Word [Signed] for the data type, and specify the number of digits of zero padding.
Count condition
Specify the condition to count output values.
Operating procedure
1.
Click the [...] button for "Count condition" in the [Data] tab on the "Data logging setting" screen.
2.
Specify the "Count condition" and "Count value" on the "Count condition" screen and click the [OK] button.
String type data/string constants are compared by the following character code.
Unicode text files, binary files: UTF-16 (little endian)
CSV files: ASCII
2 HIGH SPEED DATA LOGGER MODULE CONFIGURATION TOOL
152