Table 56 - Non-Critical 3 Diagnostic Details

Additional Status
(When a Non-Critical Device
Status is set, one or more of
the following statuses will be
set in the Additional Status
menu to provide clarification
of the cause of the failure)
Temperature:
Temp Sensor Over
Temperature
Pressure:
Press Sensor Over
Temperature
Temperature:
Sensor Input Failure
Sensor In Low Power
Mode
Sensor Input Out of
Range
SMV800 Series HART/DE Option User's Manual
Details/Resolutions
Sensor internal CPU temperature is going out of
limits. Valid Range (-40 to 85 degC).
Resolution:
Power cycle the device. If the problem still
persists make sure the environment is within
spec.
The Meter Body temperature is too high.
Accuracy and life span may decrease if it
remains high.
Resolution:
Verify the environmental temperature is within
specification. Take steps to insulate the
Temperature module from the temperature
source.
The temperature sensor (Thermocouple or RTD)
has an open input. The sensor connections may
be disconnected or broken.
Resolution:
Check the temperature sensor connections for
disconnections or broken wires.
sensor connections.
The Temperature sensor module or Pressure
sensor module is in a special low power mode
due to a Critical Status.
Resolution:
Repair the cause of the Critical Status.
The temperature sensor is reading an out of
range input value. The value is outside the
limits of Temperature limits for the
configured sensor type (LTL to UTL)
Resolution:
Check that the process temperature input is
within the range limits for the configured
temperature sensor (LTL to UTL). If a higher
temperature range is required, configure and
connect a different sensor type to meet the
requirements of the process.