DE Diagnostic Messages,
continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Output Mode PV1 (DP) STATUS
6-4
Output Mode PV2 (SP) STATUS
6-5
6-6
Output Mode PV3
(Temp)
6-7
Output Mode PV4 (Flow) STATUS
3-7
PV4 Independent
variable out of range
Page 225
Non-Critical Status Diagnostic Message Table , Continued
OUTPUT MODE PV1
#
T A G I D .
OUTPUT MODE PV1
#
OUTPUT MODE PV2
T A G I D .
OUTPUT MODE PV2
OUTPUT MODE PV3
STATUS
#
T A G I D
OUTPUT MODE PV3
OUTPUT MODE PV4
#
T A G I D .
OUTPUT MODE PV4
STATUS 3- 7
-
SMV800 Series HART/DE Option User's Manual
Possible Cause
Analog transmitter is operating as
a current source for PV1 output.
Analog transmitter is operating as
a current source for PV2 output.
Analog transmitter is operating as
a current source for PV3 output.
Analog transmitter is operating as
a current source for PV4 output.
For R250 Laminar Flow
transmitters only. Asserted when
a PV is not within the range of a
term in the laminar Flow equation.
What to Do
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the DP OutCal tab.
SFC – Press
and
[ O U T P U T ]
[ C L R ]
keys.
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the AP OutCal tab.
SFC – Press
and
[ O U T P U T ]
[ C L R ]
keys.
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the TEMP OutCal tab.
SFC – Press
and
[ O U T P U T ]
[ C L R ]
keys.
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the FLOW OutCal tab.
SFC – Press
and
[ O U T P U T ]
[ C L R ]
keys.
• Check the value of every PV
against the ranges in the
Laminar Flow equation.
• Redefine the equation, if
necessary.
Revision 6.0