Honeywell SmartLine Multivariable SMV800 Series User Manual page 234

Hart/de option
Hide thumbs Also See for SmartLine Multivariable SMV800 Series:
Table of Contents

Advertisement

DE Diagnostic Messages,
continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
3-6
Density temperature or
pressure out of range
2-2
Excess Span Correct
PV1
S p an Correction is Out
of Limits
4-2
Excess Span Correct
PV2
8-2
Excess Span Correct
PV3
222
Non-Critical Status Diagnostic Message Table , continued
-
STATUS
T A G I D .
EX . SPAN COR PV1
Or
STATUS
T A G I D .
EX. SPAN COR PV2
STATUS
T A G I D .
EX. SPAN COR PV3
SMV800 Transmitter User's Manual
Possible Cause
STATUS 3- 6
Either the temperature (PV3) or
the pressure (PV2) is not within
the boundaries of SMV steam
equation.
The SMV steam equation is
defined for pressures between 8
and 3000 psia, and temperature
between saturation and 1500
except above 2000 psia.
EX. SPAN COR PV1
#
SPAN correction factor is outside
acceptable limits for PV1 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
EX. SPAN COR PV2
#
SPAN correction factor is outside
acceptable limits for PV2 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
EX. SPAN COR PV3
#
SPAN correction factor is outside
acceptable limits for PV3 range.
What to Do
Check to see if the PV
measurement is correct.
F,
°
• Verify calibration.
• If error persists, call the
Solutions Support Center
• Verify calibration.
• If error persists, call the
Solutions Support Center
• Verify calibration.
• If error persists, call the
Solutions Support Center
Revision 6.0