Honeywell SmartLine Multivariable SMV800 Series User Manual page 236

Hart/de option
Hide thumbs Also See for SmartLine Multivariable SMV800 Series:
Table of Contents

Advertisement

DE Diagnostic Messages,
continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Input Mode PV2 (AP) STATUS
5-5
Input Mode PV3 (Temp) STATUS
5-6
Input Mode PV4 (Flow) STATUS
5-7
2-0
Meter Body Sensor Over
Temperature
2-7
No DAC Temp Comp
DAC Temperature
Compensation data is
corrupt
224
Non-Critical Status Diagnostic Message Table , continued
T A G I D .
INPUT MODE PV2
T A G I D .
INPUT MODE PV3
T A G I D .
INPUT MODE PV4
STATUS
T A G I D .
M. B. OVERTEMP
STATUS
T A G I D .
Or
NO DAC TEMPCOMP
SMV800 Transmitter User's Manual
Possible Cause
INPUT MODE PV2
#
Transmitter is simulating input
for PV2.
INPUT MODE PV3
#
Transmitter is simulating input
for PV3.
INPUT MODE PV4
#
Transmitter is simulating input
for PV4.
M. B. OVERTEMP
#
Sensor temperature is too high
(>125
span may decrease if it remains
high.
NO DAC TEMP COMP
#
Failed DAC.
What to Do
Exit Input mode:
SCT – Press "Clear Input Mode"
button on the AP InCal tab.
SFC – Press
[ C L R ]
Exit Input mode:
SCT – Press "Clear Input Mode"
button on the TEMP InCal tab.
SFC – Press
[ C L R ]
Exit Input mode:
SCT – Press "Clear Input Mode"
button on the FLOW InCal tab.
SFC – Press
[ C L R ]
Take steps to insulate meter body
C). Accuracy and life
from temperature source.
°
Replace electronics module.
and
[ S H I F T ] , [ I N P U T ] ,
keys.
and
[ S H I F T ] , [ I N P U T ] ,
keys.
and
[ S H I F T ] , [ I N P U T ] ,
keys.
Revision 6.0