Group
Parameter
Nominal
Absolute
Pressure
Nominal
(Default)
Values
Nominal
Temperature
Viscosity
Max Flow
Rate
KUser
calculation
Max
Differential
Pressure
Flow
Coefficient
(KUser)
Revision 6.0
Values
SMV800 Series HART/DE Option User's Manual
Description
The Absolute Pressure at nominal or
default process conditions. If failsafe
for the flow output is not needed
when a pressure sensor fails, the
Nominal values for pressure will be
used in the flow calculation and the
flowrate would continue to be
reported. Value is used when
Absolute Pressure Comp switch is
ON, Absolute pressure Failsafe
switch is OFF and when Absolute
pressure fails.
The Process Temperature at nominal
or default process conditions. If
failsafe for the flow output was not
needed when a temperature sensor
failed, the Nominal values for
temperature would be used in the
flow calculation and the flowrate
would continue to be reported. Value
is used when Temp Comp switch is
ON, Temp Failsafe switch is OFF
and when Temperature fails.
When Algorithm Option =
ASME 1989 Algorithms, Equation
Model = Standard.
Enter the value in the units selected
in the Unit Configuration screen.
Value cannot be <= 0
For ASME 1989 Algorithms,
Standard Compensation mode, this
value is used in calculating KUser
value. Value sent to device in kg/min
when flow type is Mass and enter in
cum/h when flow type is Volume
When Algorithm Option =
ASME 1989 Algorithms, Equation
Model = Standard.
Enter the value in the units selected
in the Unit Configuration screen.
Value must be greater than or less
than 0, but not 0.
For ASME 1989 Algorithms,
Standard Compensation mode, this
value is used in calculating KUser
value. Value sent to device in
inH2O@39degF
ASME 1989 Algorithms, Equation
Model = Standard.
Page 177