SMV 3000 Smart Multivariable Flow Transmitter
Measurements and Calculations:
Differential Pressure
Absolute or Gauge Pressure
Process Temperature via 100 ohm Pt. RTD or Type J,K,T or E Thermocouple
Mass or Volumetric Flow Rate of Air, Gases, Steam or Liquids
Key Features
Unique single capsule sensor
design provides highly
accurate measurements of
differential pressure, absolute
or gauge pressure and meter
body temperature.
3 process measurements (DP,
SP and Temp.) and a flow
calculation from one
transmitter.
Flexible Electronics design
allows RTD or Thermocouple
Input with standard wiring.
"Smart" features include
remote communication,
calibration, configuration and
diagnostics.
Flexible software allows flow
calculation for liquids, gases
and steam.
Performs dynamic mass and
volume flowrate compensation
for Orifice meters and Laminar
Flow Elements for highest
accuracy.
Honeywell Process Solutions, 2500 W. Union Hills Rd., Phoenix, AZ 85027
Figure 1 —SMV 3000 Smart Multivariable Flow Transmitter with SCT
3000 Smart Configuration Toolkit. The SMV 3000 measures differential
pressure, static pressure and process temperature, and dynamically
calculates mass or volumetric flow rate based on these measurements.
SCT 3000 ordered separately under Specification 34-CT-03-02
Standard compensation
supports other primary flow
elements:
- Venturi
- Nozzle
- Averaging Pitot Tube
Printed in U.S.A.. © Copyright 1997 — Honeywell Inc.
34-SM-03-01
Page 1 of 25
Specification and

Model Selection

Digital integration with
Honeywell control systems
provides local measurement
accuracy to the system level
without adding typical A/D and
D/A converter errors.
7/04
Guide
.

Advertisement

loading

Summary of Contents for Honeywell SMV 3000

  • Page 1: Model Selection

    Input with standard wiring. • “Smart” features include remote communication, Figure 1 —SMV 3000 Smart Multivariable Flow Transmitter with SCT calibration, configuration and 3000 Smart Configuration Toolkit. The SMV 3000 measures differential diagnostics. pressure, static pressure and process temperature, and dynamically calculates mass or volumetric flow rate based on these measurements.
  • Page 2 34-SM-03-01 Page 2 SMV 3000 Sensor and Flow Transmitter Functions Equation 1: Honeywell’s SMV 3000 Smart highly accurate pressure and Multivariable Flow Transmitter temperature compensated values ρ extends our proven “smart” for the differential pressure and = NCE technology to the measurement static pressure measurements.
  • Page 3 Discharge Coefficient Discharge coefficient is defined as the true flowrate divided by the Today, the three key With the SMV 3000, you have the theoretical flowrate and corrects measurements (differential flexibility to choose which variables the theoretical equation for the pressure, static pressure and you need to compensate.
  • Page 4 = bore diameter In turn, Beta ratio is dependent on = pipe diameter at design the bore diameter and pipe The SMV 3000 can be configured temperature diameter which are functions of to dynamically compensate for = bore diameter at design temperature.
  • Page 5 Where, averaging pitot tubes (Figure 4). Laminar Flow Elements = standard volumetric flowrate B & C = calibration constants The SMV 3000 can use either one = differential pressure µ of these methods as well as = standard viscosity = flowing temperature...
  • Page 6 Like other Smartline Transmitters, used to configure the complete used in flow applications. the SMV 3000 features two-way SMV 3000 database and save this However, there are other communication between the database for later access. The applications which require that...
  • Page 7 34-SM-03-01 Page 7 Digital Integration Links the SMV 3000 to TDC/TPS 3000 for MVA Provides Integration Greater Process Efficiency with Analog Systems Digital Integration combines the Digital Integration of the SMV 3000 The MultiVariable Analog (MVA) functions of TDC/TPS 3000...
  • Page 8: Operating Conditions

    34-SM-03-01 Page 8 SMV 3000 Specifications Operating Conditions Parameter Reference Rated Operative Transportation Condition Condition Limits and Storage °C 25 ±1 –40 to 85 –40 to 93 –55 to 125 Ambient Temperature 77 ±2 –40 to 185 –40 to 200 –67 to 257...
  • Page 9 34-SM-03-01 Page 9 SMV 3000 Specifications, continued Performance Under Rated Conditions - Differential Pressure Measurement - SMA110 Parameter Description ± 25 inH 2 O (62.5 mbar) at 39.2 °F (4 °C) standard reference temperature for Upper Range Limit inches of water measurement range.
  • Page 10 34-SM-03-01 Page 10 SMV 3000 Specifications, continued Performance Under Rated Conditions - Differential Pressure Measurement - SMA125 Parameter Description ±400 inH 2 O (1000 mbar) at 39.2 °F (4 °C) standard reference temperature for Upper Range Limit inches of water measurement range.
  • Page 11 34-SM-03-01 Page 11 Combined Zero and Span Static ±0.1.04% of calibrated span. Pressure Effect per 1000 psi (70 bar) For URV below reference point (50 inH 2 O), effect equals: • Applies for model with Stainless Steel 50 inH 2 O ...
  • Page 12 34-SM-03-01 Page 12 Combined Zero and Span Temperature In Analog Mode: ±0.35% of calibrated span. Effect per 28°C (50°F) For URV below reference point (100 inH 2 O), effect equals: • Applies for model with Stainless Steel 100 inH 2 O ...
  • Page 13 34-SM-03-01 Page 13 In Analog Mode: ±0.125% of calibrated span. Zero Temperature Effect per 28°C (50°F) For URV below reference point (50 psi), effect equals: • Applies for model with Stainless Steel 50 psi 3.5 bar barrier diaphragms ±0.025 ± 0.10 or ±0.025 ±...
  • Page 14 34-SM-03-01 Page 14 In Analog Mode: ±0.1125% of calibrated span. Zero Temperature Effect per 28°C (50°F) For URV below reference point (50 psi), effect equals: • Applies for model with Stainless Steel 50 psi 3.5 bar barrier diaphragms ±0.0125 ± 0.10 or ±0.0125 ±...
  • Page 15 34-SM-03-01 Page 15 In Analog Mode: ±0.1125% of calibrated span. Zero Temperature Effect per 28°C (50°F) For URV below reference point (300 psi), effect equals: • Applies for model with Stainless Steel 300 psi 21 bar barrier diaphragms ±0.0125 ± 0.10 or ±0.0125 ±...
  • Page 16 34-SM-03-01 Page 16 SMV 3000 Specifications, continued Performance Under Rated Conditions - Process Temperature Measurement Standards Digital Probe Type Rated Range Limits Operative Range Limits Accuracy (Ref.)* °C °F °C °F °C °F Platinum 100- ±0.6 ±1.0 –200 to 450 –328 to 842...
  • Page 17 T6 and EEx d IIC T5, T6 per ATEX standards. See attached Model Selection Guide for options. Canadian Registration Number All ST 3000 amd SMV 3000 model designs, except STG19L, STG99L, (CRN) STG170, STG180, have been registered in all provinces and territories in Canada and are marked CRN: 0F8914.5C.
  • Page 18 34-SM-03-01 Page 18 NOTE: Pressure transmitters that are part of safety equipment for the protection of piping (systems) or vessel(s) from exceeding allowable pressure limits, (equipment with safety functions in accordance with Pressure Equipment Directive 97/23/EC article 1, 2.1.3), require separate examination. millimeters Reference Dimensions: inches...
  • Page 19 3000 is 1 year after delivery. The pipe or for wall mounting. extended warranty options allow SS Center Vent/Drain and the SMV 3000 to be warranted for Bushing - CV Indicating Meter - ME up an additional 4 years. Allows a special bushing on side An analog meter is available with 0 and end vent-drain plugs.
  • Page 20 34-SM-03-01 Page 20 SMV 3000 Model Selection Guide 34-ST-16-51 Instructions Select the desired Key Number. The arrow to the right marks the selection available. Make one selection from each table, I and II, using the column below the proper arrow.
  • Page 21 34-SM-03-01 Page 21 Model Selection Guide, continued Availability SMX1XX 10 25 70 TABLE III - OPTIONS Selection None Indicating Meter Options Custom Configuration of Engineering Unit Meter Analog Meter (0-100 Even 0-10 Square Root) Engineering Unit Meter (analog mode only) Transmitter Housing &...
  • Page 22 Ex II 2 G EEx d IIC T5, T6 Int. Safe, Zone 0/1, or Flameproof, Zone 1, or Ex II 3 G EEx nA, IIC T6 (Honeywell) Enclosure IP 66/67 Non-Sparking, Zone 2 *See ATEX installation requirements in the ST 3000 User's Manual The user must determine the type of protection required for installation of the equipment.
  • Page 23 34-SM-03-01 Page 23 Model Selection Guide, continued RTD assembly available from Honeywell Inc. RTD Probe Assembly Probe Style Code 1/4-inch Rigid Probe 1/4-inch Spring-Loaded Probe Sheath Material Stainless Steel Inconel Other (Consult Phoenix STC) Probe Type 100 Ohm DIN (0.00385) Platinum...
  • Page 24 34-SM-03-01 Page 24 Model Selection Guide, continued Thermocouple assembly available from Honeywell Inc. Thermocouple Probe Assembly Probe Style Code 1/4-inch Rigid Probe 1/4-inch Spring-Loaded Probe Sheath Material Stainless Steel Inconel Other (Consult Phoenix STC) Thermocouple Type Number of Elements Single element...
  • Page 25: Ordering Information

    34-SM-03-01 Page 25 Ordering Information Contact your nearest Honeywell sales office, or In Asia: In the U.S.: In Latin America: Honeywell Asia Pacific Inc. Honeywell Honeywell Inc. Process Solutions 480 Sawgrass Corporate Parkway, Room 3213-25 Suite 200 2500 W. Union Hills Dr.