Download Print this page

Advertisement

Quick Links

SmartEye
Transmitter
Installation Instructions
7157 602
EN1B-0003UK07 0402

Advertisement

loading

Summary of Contents for Honeywell SmartEye Transmitter

  • Page 1 SmartEye Transmitter Installation Instructions 7157 602 EN1B-0003UK07 0402...
  • Page 3: Table Of Contents

    Contents Contents Contents Overview Mounting Glossary Technical data Troubleshooting EN1B-0003UK0 7 0402...
  • Page 4: Overview

    Technical terms are identified by an * and are explained in the glossary. Application − The SmartEye Transmitter is part of the SmartEye System* for wireless temperature monitoring applications. − It is a stand-alone battery operated device that measures the temperature of a wired temperature probe e.g.
  • Page 5 Overview Delivery Includes (1) SmartEye Transmitter (2) Mounting bracket (3) 2 battery cells AA 1.5V, type LR6 (mignon) e.g. Energiser LR6 or Energizer HI Energy Lithium (longer life span) (4) Temperature probe cable assembly. (Not shown) (5) TP002K temperature probe.
  • Page 6: Mounting

    Mounting Mounting Safety instructions The SmartEye Transmitter has a radio transmitter whose function can be impaired by metallic objects or radio devices. Caution! When selecting the mounting site, ensure that there is sufficient distance to metallic objects and radio devices.
  • Page 7 Mounting - Mount Transmitter with the back plate facing away from Receiver. - Mount Receiver vertically i.e. antenna pointing up or down − Mount Transmitter so that it is easily accessible for Teach-In* and battery change Information on temperature sensor & digital input Temperature Sensor Only the approved Temperature sensor (TP002K) may be used.
  • Page 8 This button is located next to the cable assembly socket and is used during the Teach-In process in the commissioning stage of the system. Mounting the SmartEye Transmitter Securing the mounting bracket The metallic mounting bracket snaps onto the back of the Transmitter.
  • Page 9 Select a suitable mounting site. Use suitable fasteners to secure the mounting bracket firmly to the mounting surface. Battery Insertion Remove the SmartEye Transmitter from the mounting bracket. Open the battery compartment: – Press in the battery lid. – Pull up the housing frame.
  • Page 10 Mounting You may be required by local law to dispose of used battery cells in a certain manner. Always replace both battery cells. Only use 1.5 V AA type LR6(mignon) cells e.g. Energizer LR6 or Energizer HI Energy Lithium (longer life span) Insert the battery cells into the battery compartment.
  • Page 11 Mounting Connecting the Temperature Probe Sensor & Digital Input Remove the lid of the interface SmartEye box on the cable assembly Transmitter I/F Insert the cabling for the TP002k probe sensor through the cable Red (Common) entry hole in the interface box. Black Screw in the stripped probe cable Green...
  • Page 12 Select a suitable mounting site. Mounting the sensor to a pipe will require a probe clip kit Honeywell Elm SF0120. Refer to Honeywell document ZD56037UK07R20801 for probe and technical data. Prepare the cables to the required length. Connect sensor to Transmitter connector as section 3.
  • Page 13 Mounting 5.3 Press Teach-In button of only one Transmitter. If Teach-In is successful, the LCD will show ‘OK’. The Transmitter is now taught into position 1 of the Receiver. 5.4 Record Location and Teach-In position of each Transmitter for future reference. 5.5 If more Transmitters remain to be taught in, press button on Receiver again to scroll to the next position and repeat steps 5.3 and 5.4.
  • Page 14 Mounting Removing a taught-in SmartEye Transmitter Required if removing/replacing a SmartEye Transmitter unit. A replacement unit must be taught in. Hold Receiver button until ‘TEACH’ is displayed. Press button to scroll through until position of device to be removed is shown.
  • Page 15: Glossary

    Genus Interface. Refer to Genus Transmitters. Interface user guide. SmartEye system Genus Wireless to Genus* temperature monitoring system. Honeywell network protocol on RS485 drivers. Teach-In Measuring data Assignment method for enabling Values which are transmitted by SmartEye Transmitters to a the SmartEye Transmitters to the SmartEye System.
  • Page 16: Technical Data

    Technical data Technical data Degree of protection IP 44 Operating temperature range –10 °C to +50 °C * Storage temperature range –20 °C to +60 °C Max. relative humidity 95% (non-condensing) Max. dimensions (W x H x D) 72 x 76 x 50 mm Power supply 2 Cells 1.5V AA type LR6 (Mignon) Alkaline or Lithium...
  • Page 17: Troubleshooting

    Insert the battery cells failed inserted incorrectly correctly. Radio connection Eliminate interf erence sources faulty (metal, radio devices). Correct the mounting site of the SmartEye Transmitter. Problem Cause Remedy SmartEye Metal obstruct- Reposition SmartEye Transmitter is ion in RF path...
  • Page 18 Also refer to the operating in- structions of the SmartEye Receiver. Problem Cause Remedy Probe fault Probe open Check probe leads reported at circuit or short connection Genus circuit Replace probe assembly equipment Teach-In Press reset/Teach-In button on carried out SmartEye Transmitter. without probe connected.
  • Page 19 Honeywell Control Products Cooling & Refrigeration Newhouse Industrial Estate Motherwell Lanarkshire ML1 5SB Scotland, United Kingdom Tel. +44 (0)1698 481698 www.honeywell-elm.co.uk Manufactured by Subject to change without notice certified to This document is definitiv e for the enclosed product and replaces all previous publications.

This manual is also suitable for:

191790