TempConf Configuration - PV3

Engineering Units
The TempConf tab card displays the Lower Range Value (LRV), Lower Range Limit (LRL), Upper
Range Value (URV) and Upper Range Limit (URL) for PV3 in the unit of measure selected in the
Engineering Units field.
Selecting PV3 Engineering Units
Select one of the preprogrammed engineering units in
depending upon output characterization configuration.
Also, select one of the preprogrammed engineering units for display of the cold junction temperature
readings (CJT Units field). This selection is independent of the other sensor measurements. See Cold
Junction Compensation on next page.

Table 10 - Pre-programmed Engineering Units for PV3

Engineering Unit
NOTE:
When output characterization configuration for PV3 is NON-LINEAR (DE
only), see Output Characterization.
PV3 input readings are displayed in the following units:
mV or V
Ohm
setting.
Cold Junction Compensation
If a thermocouple is used for process temperature PV3 input, you must select if the cold junction (CJ)
compensation will be supplied internally by the transmitter or externally from a user-supplied
isothermal block.
Specify source of cold junction temperature compensation.
Internal
Fixed - Must also key in value of cold junction temperature for reference.
Revision 6.0
d
C
Degrees Celsius or Centigrade
F
Degrees Fahrenheit
K
Kelvin
R
Degrees Rankine
milliVolts or Volts (for Thermocouple
sensor)
Ohms (for RTD sensor)
SMV800 Series HART/DE Option User's Manual
Table 10
for display of the PV3 measurements,
Meaning
d
Factory
Page 31