Table 54 - Non-Critical 1 Diagnostic Details - Honeywell SmartLine Multivariable SMV800 Series User Manual

Hart/de option
Hide thumbs Also See for SmartLine Multivariable SMV800 Series:
Table of Contents

Advertisement

Display
DD/DTM
Status
Device Status
Display Setup
Local Display
Revision 6.0

Table 54 - Non-Critical 1 Diagnostic Details

Additional Status
(When a Non-Critical
HART
Device Status is set, one or
more of the following
Tools
statuses will be set in the
Additional Status menu to
provide clarification of the
cause of the failure)
Display:
Disp Comm Failure
Disp NVM Corrupt
Comm NVM:
Display View Config
DB Corrupt
Display Common DB
Config Corrupt
Display View 1 Corrupt
Display View 2 Corrupt
Display View 3 Corrupt
Display View 4 Corrupt
Display View 5 Corrupt
Display View 6 Corrupt
Display View 7 Corrupt
Display View 8 Corrupt
SMV800 Series HART/DE Option User's Manual
Details/Resolutions
The Display has been disconnected or
configuration data has been corrupted.
Resolution:
Secure Display connections and recheck.
If problem persists, reset the device. If the
problem still persists, replace the Display.
The Local Display is reporting corruption
of the Non-Volatile Memory data (NVM )
Resolution:
Reset the device. If the problem persists,
replace the Display module.
The configuration database in the
Electronics module containing the Display
View configurations has been corrupted.
Resolution:
Check additional statuses to check which
of the Display Views is affected.
Reconfigure the affected views. If
problem persists, replace the Electronics
module and/or the Display module.
The configuration database in the
Electronics module containing the
common Display configurations has been
corrupted.
Resolution:
Reconfigure the Display setup. If problem
persists, replace the Electronics module
and/or the Display module.
If the Display View Config CB Corrupt
status is set, one or more of these detail
statuses will be set to identify the affected
View parameters.
Resolution:
Reconfigure the Display setup. If problem
persists, replace the Electronics module
and/or the Display module.