Page
Group
Analog Output
Calibration
Calibration
and
Correction
Records
DP Factory
Calibration
Selection
SP Factory
Calibration
Selection
Calibration
and
Correction
DP Method and
Records
Correction
Records
Revision 6.0
Parameter
D/A trim
Loop test
Factory Cal Available
DP
Factory Cal Available
SP
DP Zero trim
DP URV correct
DP LRV correct
DP Reset Corrects
Current URV, LRV, Zero
Trim records
Last URV, LRV, Zero
Trim records
Previous URV, LRV,
Zero Trim records
Current, last, previous
Reset correct records
SMV800 Series HART/DE Option User's Manual
Description
Perform an analog output calibration at 4.00
and 20.00 mA (0% and 100% output).
Prompts the user to connect a reference
meter to calibrate the DAC 4-20 ma output.
The output is first set to 4ma and the user
enters the actual current measured to
calibrate the DAC zero. The output is then
set to 20 ma and the user follows the same
procedure to calibrate the DAC span.
This function enables the user to test the
Analog Output measurement at any value
over the full operational range. Select a
current value to apply to the output and verify
the measured current on the loop with a
calibrated meter.
Note that this function is only available when
"Loop mA" (Loop Current mode) is Enabled.
Lists the available custom Differential
Pressure calibrations available for the
device (three custom calibrations A,B,C
are available when the device is
purchased)
Lists the available custom Differential
Pressure calibrations available for the device
(three custom calibrations A,B,C are
available when the device is purchased)
Perform an input calibration correction by
applying process input at zero
URV Correct: perform an input calibration
correction by applying process input at the
configured URV level
LRV Correct: perform an input calibration
correction by applying process input at the
configured LRV level
Date and Time of current Reset corrects
done displayed in mm/dd/yyyy format
Date and Time of current URV, LRV and
zero trim field calibration displayed in
mm/dd/yyyy format
Date and Time of last URV, LRV and zero
trim field calibration displayed in mm/dd/yyyy
format
Date and Time of previous URV, LRV and
zero trim field calibration displayed in
mm/dd/yyyy format
Date and Time of Current, Last, Previous
reset corrects displayed in mm/dd/yyyy
format
Page 115