Enter the following lower and upper Reynolds number limits in each
entry field of the Discharge Coefficient page. These values are used
to clamp the discharge coefficient equation at these Reynolds
numbers:
Click
8. Graph coordinates (Reynolds Number vs. Discharge Coefficient)
10
Enter the following equation order (order 4 is recommended) and
temperature limits for the viscosity compensation in each entry field
of the Viscosity Compensation page. The viscosity values will be
clamped at the temperature limits.
Click
9. Graph coordinates will appear when the mouse is clicked on the
graph.
Select
11
Enter the following equation order and temperature limits for the
density compensation in each entry field of the Density
Compensation page. The density values used in the flow calculation
will be clamped at the temperature limits.
Click
Graph coordinates will appear when the mouse is clicked on the
graph.
Select
Revision 6.0
Lower Limit
= 80,000
Upper Limit
= 800,000
to proceed to the Viscosity Compensation page.
Next
will appear when the mouse is clicked on the graph.
Order
= 4
Low Temp
= 50
High Temp
= 150
to refit the curve with the new limits.
Yes
to proceed to the Density Compensation page.
Next
Order
= 4
Low Temp
= 50
High Temp
= 150
to refit the curve with the new limits.
Yes
to proceed to the Flowing Variables page.
Next
SMV800 Transmitter User's Manual
Page 281