Installing a Multiservice Switch 7440 into a rack or cabinet

Install a Nortel Multiservice Switch 7440 into a rack or cabinet. The mounting
brackets bolt into the side rails of the rack or cabinet.
Prerequisites
If you plan to install the device in a Nortel Multiservice Switch cabinet,
check the position of the uprights. You must set the front uprights back
11.4 cm (4.5 in.) from the front of the cabinet. The spacing between front
and rear uprights must be 36.8 cm (14.5 in.).
Install and ground the rack or cabinet before proceeding. For more
information, see
Ground yourself to an appropriate anti-static discharge apparatus while
handling the shelf assembly (device).
Procedure steps
Step
1
2
3
Copyright © 2005, Nortel
- 203 -
Hardware procedures
Cabinet installation (page
Action
Secure the left and right rack-mounting brackets to the rack. Insert the
4 screws into the holes in each bracket and into the respective holes in the
rack. Then, fasten the screws. See the figure
brackets to a rack (page
204).
Secure the rack-mounting crossmember to the rear of the rack-mounting
brackets with the 2 screws provided. See the figure
mounting brackets to a rack (page
Place the device on the rack-mounting brackets. Use the two remaining
screws to fasten the chassis to the right-hand bracket. Ensure that the rear
of the device is fully seated on the rack-mount brackets. See the figure
Securing the chassis to a rack (page
Nortel Multiservice Switch 7400
Hardware Installation, Maintenance, and Upgrade
NN10600-175 7.1S1 Standard
PCR7.1 and up October 2005
61).
Securing the rack-mounting
Securing the rack-
204).
205).
--End--