Procedure steps
Step
1
2
3
4
5
Procedure job aid
Pinouts of the connectors for DS1 or E1 balanced
Pin
1
2
3
4
5
6
7
8
9
Copyright © 2005, Nortel
- 311 -
Hardware procedures
Action
Lay the wires from the timing source up to the connectors on the BITS
termination panel. Route the wires up or down the right side of the frame
against the cable management brackets.
Connect the wires at the timing source, using whatever method of
connection is required.
Label each timing wire pair at both end points to distinguish which is
reference 0 and which is reference 1.
Fasten the wires snugly with tie-wraps to whatever CPE wire support system
leads to the cable management brackets on the mounting apparatus. Leave
enough length at termination panel end of the wire to attach the D-sub or
coax connectors.
Assemble the cable with the appropriate connector. Refer to the pinout
tables below.
DS1 for SETS-0
no connection
no connection
GND (ground)
no connection
BITSRX0P
no connection
no connection
no connection
BITSRX0N
Nortel Multiservice Switch 7400
Hardware Installation, Maintenance, and Upgrade
NN10600-175 7.1S1 Standard
PCR7.1 and up October 2005
--End--
DS1 for SETS-1
no connection
no connection
GND (ground)
no connection
BITSRX1P
no connection
no connection
no connection
BITSRX1N