Installing the switch in an equipment rack

Required tool: #2 Phillips screwdriver for attaching brackets to the switch.
Rack requirements:
1
2
A space of 1.75 inches is provided for each switch in an EIA or IEC standard
19-inch (48.2-centimeter) equipment rack.
The rack is bolted to the floor and braced if necessary.
The rack is grounded to the same grounding electrode used by the power
service in the area. The ground path must be permanent and must not exceed 1
ohm of resistance from the rack to the grounding electrode.
Attach a bracket to each side of the switch.
Slide the switch into the rack. Insert and tighten the rack-mount screws.