Routing Card Cables On A Multiservice Switch 7480; Nortel Multiservice Switch 7400 Hardware Installation, Maintenance, And Upgrade - Nortel Multiservice Switch 7400 Installation & Maintenance

Table of Contents

Advertisement

Routing card cables on a Multiservice Switch 7480

Route processor card cables through the cable management assembly on top
of the Nortel Multiservice Switch 7480 to keep them organized.
Procedure steps
Step
1
2
3
4
5
Copyright © 2005, Nortel
- 448 -
Hardware procedures
Action
Open the cable management assembly door.
Route the cables from the faceplate of each processor card through the
cable management assembly above the shelf assembly. The smaller
channels in the cable guides are for fiber optic cables. See the figure
Routing cables through a cable management assembly for a Multiservice
Switch 7480 (page
449).
Label all processor card cables near the connector to indicate the if it is a
receive or transmit cable.
Secure cables to the sides of the cabinet to ensure that proper airflow
around the shelves. Always ensure that you do not pinch cables, especially
fiber cables.
Close the cable management assembly door to hold the cables in place.
Nortel Multiservice Switch 7400
Hardware Installation, Maintenance, and Upgrade
NN10600-175 7.1S1 Standard
PCR7.1 and up October 2005
--End--