Commissioning
12.3 Procedure for commissioning the S7-1500 automation system
Requirements: CPU as bus device
Note the following requirements for operation of a CPU as bus device:
• PROFIBUS interface
– The integrated PROFIBUS interface of the CPU is configured using STEP 7 (device
– The CPU is connected to the subnet.
– The terminating resistors at the segment boundaries are switched on.
You can find more information in the PROFIBUS function manual
(https://support.industry.siemens.com/cs/ww/en/view/59193579)
• PROFINET interface
– The integrated PROFINET interface of the CPU is configured using STEP 7 (IP address
– The CPU is connected to the subnet.
You can find more information in the PROFINET function manual
(https://support.automation.siemens.com/WW/view/en/49948856)
Procedure for commissioning a SIMATIC Safety F-system
The procedure for commissioning an F-system is essentially the same as for commissioning a
standard system. You use the Safety Administration Editor to commission SIMATIC Safety and
activate the safety mode. The Safety Administration Editor is assigned to the fail-safe CPU in
the STEP 7 project tree.
You can find more information on commissioning a SIMATIC Safety F-system and the Safety
Administration Editor in the programming and operating manual SIMATIC Safety –
Configuring and Programming
(https://support.industry.siemens.com/cs/ww/en/view/54110126).
12.3.1

Removing/inserting a SIMATIC memory card on the CPU

Requirements
The CPU only supports pre-formatted SIMATIC memory cards. If applicable, delete all
previously stored data before using the SIMATIC memory card. Additional information about
deleting the contents of the SIMATIC memory card can be found in the function manual
Structure and use of the CPU memory
(https://support.industry.siemens.com/cs/ww/en/view/59193101).
In order to work with the SIMATIC memory card, first ensure that the SIMATIC memory card is
not write-protected. For this purpose, slide the slider on the SIMATIC memory card out of the
lock position.
If the inserted SIMATIC memory card is write-protected, the CPU display outputs the symbol
in the menu "Memory card" > "Overview". In addition, the display shows a message in the
lower level of the menu.
258
address and bus parameters configured).
and device name configured).
Automation system
System Manual, 01/2023, A5E03461182-AK