Commissioning guideline

3.14 Removing and inserting of modules

3.14
Removing and inserting of modules
Pulling and plugging digital electronics module 8 DI NAMUR
1. Swing the first of the three 8 DI NAMUR electronic modules out from the terminal module
during operation.
2. Observe the status LEDs.
For PROFINET configuration - LEDs on the interface module IM 152-1PN of the ET 200iSP:
– ER: on (means: LED lights up)
– MT: off (means: LED does not light up)
– ACT: On
– RN: On
– PS1: On, PS2: Off
– LK1 and/or LK2: on (when a network connection is set up from one device to another;
For PROFIBUS configuration - LEDs on the interface module IM 152-1DP of the ET 200iSP:
– SF: on --> diagnostic message is available.
– BF: Off
– ON: On
– PS1: On, PS2: Off
Result: The ET 200iSP continues operating without fault.