Technology Module For Time-Based Io - Siemens SIMATIC S7-1500/ET 200MP System Manual

Hide thumbs Also See for SIMATIC S7-1500/ET 200MP:
Table of Contents

Advertisement

System overview
4.8 Technology functions
4.8.5

Technology module for time-based IO

Time-based IO modules enable you to achieve maximum precision and speed - regardless of
the performance of the controller and the fieldbus. The time-based IO modules output signals
with a precisely defined response time. The I/O signals are processed on a time basis.
The table below shows the main features of the technology module for time-based IO. In
conjunction with the "Output cam" and "Cam track" technology objects, the TM Timer DIDQ
16x24V ensures highly accurate cam output. In conjunction with the "Measuring input"
technology object, the TM Timer DIDQ 16x24V ensures highly accurate detection of passing
products.
Short designation
Article number
Manual
Connectable encoders
Max. count frequency
Integrated DI
Integrated DQ
Diagnostic interrupt
Hardware interrupt
Isochronous mode
Benefits
The technology modules for time-based IO offers you the following advantages:
• Meets stringent requirements for precision and speed, independent of the CPU and
fieldbus
• Signals are read in and output precisely, to within 1 microsecond
• Exact definition of response times, independent of the application cycle
• Typical use: cam control, length measurement, time measurement, as a probe, for dosing
fluid quantities
94
TM Timer DIDQ 16x24V
6ES7552-1AA00-0AB0
Link
24 V incremental encoder with signals A and B
24 V pulse encoder with a signal
200 kHz with fourfold evaluation
Up to 8 DIs with the following functions:
Up to 2 time stamps per cycle (resolution 1 µs)
32x oversampling
Counting function up to 50 kHz
Incremental encoder acquisition with 2 phase-shifted tracks
Configurable input filter to suppress interference
Up to 16 DQs with the following functions:
Up to 2 time stamps per cycle (resolution 1 µs)
32x oversampling
Pulse-width modulated output
Configurable substitute values per DQ
X
---
X (required for the time stamp and oversampling functions)
Automation system
System Manual, 01/2023, A5E03461182-AK