Options for reading out I&M data
• Via the user program
• Using the display of the CPU
• Via STEP 7 or HMI devices
• Via the CPU web server
Reading I&M data via the user program
You have the following options for reading module I&M data in the user program:
• Using the RDREC instruction
The data record structure for centrally inserted modules as well as for distributed modules
that are accessible via PROFINET IO/PROFIBUS DP is described in the section Record
structure for I&M data (Page 285).
• Using the Get_IM_Data instruction
Reference
The description of the instructions can be found in the STEP 7 online help.
Reading I&M data from displays
To read the I&M data "Plant designation" or "Location identifier" of the CPU via the display,
follow these steps:
1. Navigate to the "Overview/PLC" menu on the display of the CPU.
2. Select "Plant designation" or "Location identifier" and confirm with "OK".
To read the I&M data "Plant designation" or "Location identifier" of a centrally used module,
follow these steps:
1. Navigate to the "Modules" menu on the display of the CPU.
2. Select the menu command "Local modules" and confirm with "OK".
3. Select the slot of the module (e.g., slot 3: DI 32 x 24VDC HF) and confirm with "OK".
4. Select the "Status" and confirm with OK.
5. Select "Plant designation" or "Location identifier" and confirm with "OK".
To read the I&M data "Plant designation" or "Location identifier" of a module used in
distributed mode, follow these steps:
1. Navigate to the "Modules" menu on the display of the CPU.
2. Select the corresponding distributed I/O system (for example PROFINET IO system) and
confirm with "OK".
3. Select the corresponding device (for example ET 200SP-Station_1) and confirm with "OK".
4. Select the slot of the module (e.g., slot 1: DI 16 x DC24V ST_1) and confirm with "OK".
5. Select the "Status" and confirm with OK.
6. Select "Plant designation" or "Location identifier" and confirm with "OK".