Application planning
5.1 Hardware configuration
5.1.3
Hardware configuration of the ET 200MP distributed I/O system with
PROFIBUS interface module
Maximum configuration
The integrated system power supply of the interface module feeds 14 W into the backplane
bus. You can insert a maximum of 12 modules to the right of an interface module. The power
budget calculation determines the exact number of I/O modules that can be operated with
the interface module. The operating principle is described in section Power balance
calculation (Page 121).
Figure 5-3
Applicable modules
The following table shows which modules may be used in the various slots:
Table 5- 3
Module type
Interface module
Analog and digital I/O modules
Communications modules
Point-to-point
Technology modules
110
Maximum configuration ET 200MP with IM 155-5 DP
Assignment of slot numbers
Permissible slots
2
3 - 14
3 - 14
3 - 14
System Manual, 01/2023, A5E03461182-AK
Maximum number
of modules
1
12
12
12