Siemens SIMATIC S7-1500/ET 200MP System Manual page 349

Hide thumbs Also See for SIMATIC S7-1500/ET 200MP:
Table of Contents

Advertisement

Technical specifications
16.2 Electromagnetic compatibility
Sinusoidal disturbances
The following table shows the electromagnetic compatibility of the S7-1500 automation
system/ET 200MP distributed I/O system with regard to sinusoidal disturbances (RF radiation).
Table 16- 2
RF radiation in accordance with IEC 61000-4-3/NAMUR 21
Electromagnetic RF field, amplitude-modulated
80 GHz to 2.7 GHz
2.7 GHz to 6 GHz
80 % AM (1 kHz)
The following table shows the electromagnetic compatibility of the S7-1500 automation
system/ET 200MP distributed I/O system with regard to sinusoidal disturbances (RF coupling).
Table 16- 3
RF coupling in accordance with IEC 61000-4-6
from 10 kHz
10 V
80 % AM (1 kHz)
150 Ω source impedance
Emission of radio interference
Interference emission of electromagnetic fields in accordance with EN 55016.
Table 16- 4
Frequency
30 MHz to 230 MHz
230 MHz to 1000 MHz
from 1 to 3 GHz
from 3 to 6 GHz
Interference emission via the AC power supply according to EN 55016.
Table 16- 5
Frequency
0.15 MHz to 0.5 MHz
0.5 MHz to 30 MHz
348
Sinusoidal disturbances with RF radiation
Sinusoidal disturbances with RF coupling
rms
Interference emission of electromagnetic fields
Interference emission via the AC power supply
10 V/m
3 V/m
Interference emission
< 40 dB (µV/m) QP
< 47 dB (µV/m) QP
< 76 dB (µV/m) P
< 80 dB (µV/m) P
Interference emission
< 79 dB (µV/m)Q
< 66 dB (µV/m) M
< 73 dB (µV/m)Q
< 60 dB (µV/m) M
System Manual, 01/2023, A5E03461182-AK
Corresponds to degree
of severity
3
2
Corresponds to degree
of severity
3
Measuring distance
10 m
10 m
3 m
3 m
Automation system

Advertisement

Table of Contents
loading

Table of Contents