Procedure
To set up the configuration control, proceed as follows:
Table 11- 1
Procedure for commissioning the SIMATIC S7-1500
Step
Procedure
1
Enable configuration control in STEP 7
2
Create control data record
3
Transfer control data record
Library for configuration control
A library for configuration control is available for download
(https://support.industry.siemens.com/cs/ww/en/view/29430270) on the internet. The library
contains data types with the structure of the control data records for the S7-1500/ET 200MP
automation system. You can implement the configuration control for your flexible
automation solution economically using these data types.
11.2.1

Configuring

Requirements
In the case of the S7-1500, configuration control is possible both with centrally inserted
modules and with the ET 200MP distributed I/O system via PROFINET IO.
For S7-1500 automation system:
• STEP 7 Professional as of Version V13
• CPU S7-15XX as of firmware version V1.5
• The startup parameter "Comparison preset to actual configuration" is set to "Startup CPU
even if mismatch" (default setting).
You can find the "Comparison preset to actual configuration" parameter in the Inspector
window of the CPU properties under "General">"Startup".
For ET 200MP distributed I/O system:
• STEP 7 Professional as of Version V13
• IM 155-5 PN ST/HF
• You have assigned the interface module to an IO controller/DP master in STEP 7
• The startup parameter "Comparison preset to actual module" is set to "Startup CPU even if
mismatch" (default setting).
You can find the "Comparison preset to actual module" parameter in the Inspector window
of the interface module properties in the "Startup" field under "General">"Module
parameters".
Automation system
System Manual, 01/2023, A5E03461182-AK
11.2 Configuration control (option handling)
See...
Section Configuring (Page 239)
Section Creating the control data record (Page 241)
Section Transferring the control data record in the startup pro-
gram of the CPU (Page 250)
Flexible automation concepts
239