Stop Mode; Run Mode - Siemens SIMATIC S7-1500/ET 200MP System Manual

Hide thumbs Also See for SIMATIC S7-1500/ET 200MP:
Table of Contents

Advertisement

Example for the "Comparison preset to actual configuration" parameter
"Startup CPU only if compatible"
The DI 32x24VDC HF input module with 32 digital inputs can be a compatible replacement
for a DI 16x24VDC HF input module with 16 digital inputs. The pin assignment and all
electrical and functional properties are identical.
"Startup CPU even if mismatch"
Instead of a configured digital input module, you insert an analog output module or no
module is present in this slot and thus in all subsequent slots. Although the configured inputs
cannot be accessed, the CPU starts up.
Note that the user program cannot function correctly in this case. Therefore, take appropriate
measures!
12.5.2

STOP mode

Response
The CPU does not execute the user program in STOP mode.
All outputs are disabled or react according to the parameter settings for the respective
module: They provide a substitute value as set in the parameters or retain the last value
output and thus hold the controlled process in a safe operating mode.
12.5.3

RUN mode

Response
In "RUN" mode the cyclic, time-driven, and interrupt-driven program execution is performed.
Addresses that are in the "Automatic Update" process image are automatically updated in
each program cycle. For additional information, see section Process images and process
image partitions (Page 203).
Automation system
System Manual, 01/2023, A5E03461182-AK
Commissioning
12.5 Operating modes
267