Cpu Memory Reset - Siemens SIMATIC S7-1500/ET 200MP System Manual

Hide thumbs Also See for SIMATIC S7-1500/ET 200MP:
Table of Contents

Advertisement

12.6

CPU memory reset

Basics of a memory reset
The CPU must be in STOP mode for a memory reset.
A memory reset returns the CPU to its "initial state".
Memory reset means:
• An existing online connection between your programming device/PC and the CPU is
terminated.
• The content of the work memory and the retentive and non-retentive data are deleted
(with manual memory reset).
• The diagnostics buffer, time of day, and IP address are retained.
• Subsequently the CPU is initialized with the loaded project data (hardware configuration,
code and data blocks, force jobs). The CPU copies this data from the load memory to the
work memory.
Result:
– If you set an IP address in the hardware configuration ("Set IP address in the project"
– Data blocks no longer have current values but rather their configured start values.
– Force jobs remain active.
Detecting a CPU memory reset
The RUN/STOP LED flashes yellow at 2 Hz. After completion, the CPU switches to STOP. The
RUN/STOP LED is on (constant yellow light).
Result after memory reset
The following table provides an overview of the contents of the memory objects after
memory reset.
Table 12- 4
Memory objects after memory reset
Memory object
Actual values of the data blocks, instance data blocks
Bit memories, timers and counters
Retentive tags of technology objects
(e.g. adjustment values of absolute encoders)
Diagnostics buffer entries
IP address
Device name
Counter readings of the runtime meters
Time of day
CPU operating state: RUN/STOP
Only with standard, F-CPUs/compact CPUs as of article number 6ES751x-xxx02-0AB0/6ES751x-1CK01-0AB0
1)
Automation system
System Manual, 01/2023, A5E03461182-AK
option) and a SIMATIC memory card with the project is in the CPU, this IP address is
valid after the memory reset.
1)
Contents
Initialized
Initialized
Retained
Retained
Retained
Retained
Retained
Retained
The CPUs retain the RUN or STOP state.
Commissioning
12.6 CPU memory reset
271