Flexible automation concepts
11.2 Configuration control (option handling)
11.2.2.3

Feedback data record of the ET 200MP distributed I/O system

Operating principle
The feedback data record informs you about the accuracy of the module assignment and
gives you the option of detecting assignment errors in the control data record. The feedback
data record is mapped via a separate data record 197 V2.0.
Slot assignment
The feedback data record exists only when configuration control is configured and always
refers to the maximum quantity framework without interface module, i.e., 31 slots.
The following table shows the slot assignment of the modules:
Table 11- 6
Slot assignment
Slot
Modules
0
System power supply (optional)
2 - 31
I/O modules/system power supplies, depending on
the station option
Partial reading of the feedback data record is possible.
Feedback data record
Table 11- 7
Feedback data record
Byte
0
1
2
3
4
5
6
7
:
64
65
* Not possible if the slot is marked as not available.
246
Element
Block length
Block ID
Version
Status slot 0
Reserved
Status slot 2
Reserved
:
Slot n status
Reserved
Comment
Upstream from interface module
Downstream from the interface module
Code
66
197
2
0
0/1
0
0/1
0
:
Maximum slot
0
System Manual, 01/2023, A5E03461182-AK
Explanation
Header
Status = 1:
Module from station master is
inserted in the station option
Slot is marked as not available
in the control data record
Status = 0:
Module pulled
Incorrect module inserted in
the station option*
Automation system